Setting the Frequency Reference
Chapter 5-5
5-5-4
Setting Frequency References through Key Sequences
The following description provides information on parameters related to
frequency reference settings through key sequences on the Digital Operator
Setting Frequency References 1 through 8 and the Inching Frequency
Command (n21 through n28 and n29)
A total of nine frequency references (frequency references 1 through 8) and
an inching frequency command can be set together in the Inverter.
Setting Frequency References 1 through 8 (n21 through n28)
Note
1.
Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz
and 1-Hz increments if the frequency is 100 Hz or over.
2.
Frequency reference 1 is enabled with n03 for frequency reference
selection set to 1.
3.
Frequency references 2 through 8 are enabled by setting multi-step speed
references 1, 2, and 3 in n36 through n39 for multi-function input. Refer to
the following table for the relationship between multi-step speed references
1 through 3 and frequency references 1 through 8.
n21
Frequency Reference 1
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
6.0
n22
Frequency Reference 2
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
0.0
n23
Frequency Reference 3
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
0.0
n24
Frequency Reference 4
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
0.0
n25
Frequency Reference 5
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
0.0
n26
Frequency Reference 6
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
0.0
n27
Frequency Reference 7
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
0.0
n28
Frequency Reference 8
Changes during
operation
Yes
Setting
range
0.0 to max. frequency
Unit of
setting
0.01 Hz
(see note 1)
Default setting
0.0
Содержание J7 series
Страница 12: ...XII...
Страница 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Страница 47: ...33 CHAPTER 3 Preparing for Operation and Monitoring 3 1 Nomenclature 34 3 2 Outline of Operation 35...
Страница 54: ...40 Outline of Operation Chapter 3 2...
Страница 102: ...88 Other Functions Chapter 6 7...
Страница 158: ...144 Option Specifications Chapter 9 3...
Страница 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Страница 172: ...158 List of Parameters Chapter 10...
Страница 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...