54
Ch
apt
e
r
3
In
st
alla
tion Condit
io
ns
F3SJ-A
User’s Manual
Wiring/Installation
When using 4 or more sets that are not series-connected, the installations shown below may cause
mutual interference. When mutual interference occurs, the F3SJ enters lockout.
Distance between emitter and
receiver (operating range L)
Allowable installation distance D
For 0.2 to 3m
0.26m
For 3m or more
L x tan5 ° = L x 0.088 (m)
Emitter 1
Receiver 1 Emitter 2
Receiver 2
Emitter 1
Receiver 1
Receiver 2
Emitter 2
Aligned horizontally
Aligned fore and aft
Emitter 1
Receiver 1
Emitter 2
Receiver 2
Aligned vertically
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles