F3SJ-A
User’s Manual
System Configuration and Functions
Wiring for auto reset mode
Wiring the emitter’s circuit as shown below provides auto reset mode.
Wiring when external device monitoring function is not used
Disable the external device monitoring function by connecting auxiliary output 1 and the external
device monitoring input as shown in the diagram below.
4
1
+24V DC
S3
Open
Emitter side
(WHITE) Interlock selection input
(YELLOW) Reset input
S3
: Lockout reset switch
(connect to 24V if a switch is not required)
0V
K3
*1
Receiver side
(Yellow) Auxiliary output 1
(Red) External device monitoring input
*1 If K3 is not required, connect auxiliary output 1 to external
device monitoring input only.