134
Analog Output Units
Section 5-2
Wiring
Attach MOLEX connectors to the analog output connectors, and connect the
outputs as shown in the following diagram.
Applicable Connectors
Output Ranges and
Converted Data
The Analog Output Unit converts the digital output data to analog values. The
analog values depend on the output signal ranges, as shown in the following
diagrams.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
Manufac-
turer
Connector
Model number
Remarks
MOLEX
Pressure-
welded
Housing
521-09-0390
For AWG#24
Crimp
Housing
50-57-9403
Reeled contacts
16-02-0069
For AWG#24 to 30
16-02-0086
For AWG#22 to 24
Loose contacts
16-02-0096
For AWG#24 to 30
16-02-0102
For AWG#22 to 24
Crimping tool
570-36-5000
For AWG#22 to 26
11-01-0209
For AWG#24 to 30
External
device
Power
supply
24 VDC
+
−
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
(
−
300)
1770
(6000)
189C
(6300)
8000
0000 (0)
7FFF
Converted data
Hexadecimal
(Decimal)
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...