137
Analog Output Units
Section 5-2
5-2-3
Settings Using the Configurator
The output range and the output for communications errors for the Analog
Output Unit can be set using version 1.11 or later of the DeviceNet Configura-
tor (referred to as the Configurator below). Using Ver. 1.20 or later, you can
also adjust or clear the offset and gain settings.
Setting the Output Range
and Output for
Communications Errors
Use the following procedure to set the output range. The DeviceNet and the
MULTIPLE I/O TERMINAL must be connected first.
Note The output range can be set for each point using the Configurator.
Ranges can be set in 2-point units using DIP switches.
1,2,3...
1.
Set pin 10 of the DIP switch for the Analog Output Unit to ON to set the
Software Setting Enable/Disable setting to enable.
2.
Turn the power supply ON for all the Units of the MULTIPLE I/O TERMI-
NAL, including the Analog Unit and the Communications Unit.
3.
Connect the Configurator to the DeviceNet network, making it online.
4.
On the device list for the Configurator, double-click the Communications
Unit to which the Analog Output Unit is connected.
The Edit Device Parameters window for the Communications Unit that is
double-clicked, will be displayed.
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...