114
Analog Input Units
Section 5-1
5-1-3
Settings Using the Configurator
The input range for the Analog Input Unit can be set using version 1.11 or
later of the DeviceNet Configurator (referred to as the Configurator below).
Using Ver. 1.20 or later, you can also adjust or clear the offset and gain set-
tings.
Input Range Settings
Use the following procedure to set the input range. The DeviceNet and the
MULTIPLE I/O TERMINAL must be connected first.
Note The input range can be set for each point using the Configurator.
Ranges can be set in 2-point units by setting DIP switches.
1,2,3...
1.
Using the DIP switch for the Analog Input Unit, make the Software Setting
Enable/Disable setting to enable by making the following pin settings:
GT1-AD04:
Set pin 10 to ON.
GT1-AD08MX: Set pin 16 to ON.
2.
Turn ON the power supply for all the Units of the MULTIPLE I/O TERMI-
NAL, including the Analog Unit and the Communications Unit.
3.
Connect the Configurator to the DeviceNet network, making it online.
4.
On the device list for the Configurator, double-click the Communications
Unit to which the Analog Input Unit is connected.
The Edit Device Parameters window for the Communications Unit that is
double-clicked, will be displayed.
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...