![background image](http://html1.mh-extra.com/html/omron/drt1-com/drt1-com_operation-manual_742286142.webp)
132
Analog Output Units
Section 5-2
DIP Switch Settings
The following diagram shows the functions of the DIP switch.
The following table summarizes the DIP switch settings. (All pins are factory-
set to OFF.)
Note
1.
When setting the output range or output for communications errors using
a DeviceNet Configurator, use version 1.11 or later. (If pin 10 is ON, and a
setting is made using the Configurator, the output ranges will all be 0 to 5
V and the output for communications errors setting will be set to clear to
minimum.)
2.
Make sure the I/O Unit power supplies (including the I/O Unit interface
power supply) are OFF when setting the DIP switch.
3.
With an Analog Output Unit, outputs for communications errors is enabled
using the switch on the Analog Output Unit. It does not depend on the
Communications Unit “hold/clear communications error” setting.
Output Range Settings
As shown in the following table, the DIP switch output range settings are for
two outputs each.
Pin(s)
Function
Settings
Meaning
1 through 6
Output range
Output range settings (See below.)
7
Reserved for system use
OFF
Must be set to OFF.
8, 9
Output for communications
errors
(See below.)
8
9
Output
OFF
OFF
Clear to minimum
(See below.)
OFF
ON
Clear to maximum
(See below.)
ON
OFF
Clear to 0 V
(for –10 to 10 V)
Clear to minimum
(other than the above)
ON
ON
Hold
10
Software setting enable/
disable
OFF
Set the output range, and
output for communications
errors, with pins 1 to 9. (fac-
tory-set)
ON
Output range setting (See
note.) and output setting for
communications errors can
be set using the Configura-
tor.
Operating specifications
Output for communications errors
Software setting enable/disable
Output
range
ON
Pin 1
Pin 2
Pin 3
Output range settings for outputs 0 and 1
Pin 4
Pin 5
Pin 6
Output range settings for outputs 2 and 3
OFF
OFF
OFF
0 to 5 V (factory-set)
ON
OFF
OFF
1 to 5 V
OFF
ON
OFF
0 to 10 V
ON
ON
OFF
–10 to 10 V
Other than the above
Cannot be set
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...