Analog Input Units
Section 5-1
to 20 mA and the current drops below 3.2 mA. When the opencircuit detection
function is activated, the converted data will be set to 7FFF.
The open-circuit detection function is enabled or cleared when data is con-
verted. If the input returns to the convertible range, the open-circuit detection
is cleared automatically and the output returns to the normal range.
Common Power Supply
for Input Devices
If an open-circuit occurs when more than one input device is using the same
power supply, and voltage input is being supplied, the following situation will
occur (this does not apply when current input is being supplied).
If an open-circuit occurs at A in the above diagram, a sneak circuit will be cre-
ated in the direction of the arrow, and even though the circuit is open, a volt-
age will exist. This voltage will be approximately 1/3 to 1/2 of the output of the
input devices in the part of the circuit that is not open. (The same will apply if
an open circuit occurred at B.) With such a voltage present in the circuit, the
open-circuit will not be detected. When voltage input is being supplied, either
set up the input devices so that they are not using the same power supply, or
use isolators for each input.
Converted Data
Power
supply
Input
device
Input
device
Analog Input Unit
Voltage
occurrence
Internal
circuits
−
−
Bit
First word
First word + 1
First word + 2
First word + 3
Input 0 converted data
Input 1 converted data
Input 2 converted data
Input 3 converted data
For 8 Inputs
For 4 Inputs
Bit
First word
First word + 1
First word + 2
First word + 3
Input 0 converted data
Input 1 converted data
Input 2 converted data
Input 3 converted data
First word + 4
First word + 5
First word + 6
Input 4 converted data
Input 5 converted data
Input 6 converted data
First word + 7
Input 7 converted data
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...