180
GT1-CT01 Counter Unit
Section 5-4
The possible combinations (reset modes) are shown in the following table.
Note
1.
Setting of the reset mode is performed in bits 12 to 14 in word n+2 of the
output area.
2.
The Counter Unit will execute reset with the first count following the fulfill-
ment of the reset conditions.
3.
Encoder input Z is only effective for the rising edge. When using the encod-
er input Z under AND conditions with other inputs, ensure that encoder in-
put Z will turn ON last.
4.
When repeating reset for the count value, allow an interval of at least 0.1
ms before switching ON the encoder input Z and at least 1 ms before
switching ON the external inputs.
5.
It is not possible to execute ON/OFF timing for the internal Reset Bit with
perfect accuracy, due to the communications time required for remote I/O
communications.
Count Value Setting
The count value (the present value) for the Counter Unit can be set as
required, to any value in range –8,388,608 to +8,388,607. Count value setting
can be performed in BCD or hexadecimal.
Note
1.
Count value setting is performed by setting a value in words n, n+1 of the
output area as shown below, and switching ON the Count Value Setting Bit
(word n+2, bit 02).
Reset mode
Input
Counter reset condition and timing
1
Encoder input Z
2
External input
3
Encoder input Z + exter-
nal input
4
Internal Reset Bit
5
Encoder input Z + inter-
nal Reset Bit
6
External inter-
nal Reset Bit
7
Encoder input Z + exter-
nal input + internal Reset
Bit
Encoder input Z
Reset
External input
Reset
Encoder input Z
External input
Reset
Internal Reset Bit
Reset
Encoder input Z
Internal Reset Bit
Reset
External output
Internal Reset Bit
Reset
Encoder input Z
External input
Internal Reset Bit
Reset
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...