109
Analog Input Units
Section 5-1
Applicable Connectors
Input Ranges and Converted Data
The Analog Input Unit converts analog input data to digital values. The digital
values depend on the input signal ranges, as shown in the following diagrams.
When the input exceeds the specified range, the AD conversion data will be
fixed at either the lower limit or upper limit.
–10 to 10 V
The –10- to 10-V range corresponds to the hexadecimal values F448 to 0BB8
(–3000 to 3000). The entire data range is F31C to 0CE4 (–3300 to 3300). A
negative voltage is expressed as a two’s complement (16 bits). If the line is
disconnected, the data will be the same as an input of 0 V (0000 Hex).
0 to 10 V
The 0- to 10-V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The entire data range is FED4 to 189C (–300 to 6300). A negative
Manufac-
turer
Connector
Model number
Remarks
MOLEX
Pressure-
welded
Housing
521-09-0390
For AWG#24
Crimp
Housing
50-57-9403
---
Reeled contacts
16-02-0069
For AWG#24 to 30
16-02-0086
For AWG#22 to 24
Loose contacts
16-02-0096
For AWG#24 to 30
16-02-0102
For AWG#22 to 24
Crimping tool
570-36-5000
For AWG#22 to 26
11-01-0209
For AWG#24 to 30
Voltage input
connection
Current input
connection
24 VDC
Source
24 VDC
0 V
0 V
0CE4 (3300)
0BB8 (3000)
−
11 V
−
10 V
0 V
10 V 11 V
F448 (
−
3000)
F31C (
−
3300)
0000 (0)
Converted data
Hexadecimal (Decimal)
Voltage
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...