148
GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
5-3
GT1-TS04T and GT1-TS04P Temperature Input Units
5-3-1
Specifications
General Specifications
Characteristics
Note K or T below –100
°
C:
±
2
°
C
±
1 digit max.
L:
±
2
°
C
±
1 digit max.
R or S below 200
°
C:
±
3
°
C
±
1 digit max.
B below 400
°
C:
No standard set
Item
Specification
I/O connections
M3 terminal block
Number of inputs
4 points (Allocated 4 words or 8 words in the mas-
ter. The number of allocated words can be set using
the DIP switch.)
Internal
power sup-
ply
Voltage range
20.4 to 26.4 VDC (–15 to 10% at 24 VDC)
Current consump-
tion in Unit (inrush
current)
80 mA max.
(Inrush current 10 A max., pulse width 1 ms max.)
Current consumption
(I/O Unit interface)
50 mA max.
Noise immunity
±
2000 V
(IEC61000-4-4 via fast transient noise simulator)
Vibration resistance
10 to 150 Hz, 0.7-mm double amplitude or 50 m/s
2
Shock resistance
150 m/s
2
Ambient temperature
–10
°
C to 55
°
C
Ambient humidity
25% to 85% (with no condensation)
Operating atmosphere
No corrosive gases
Storage temperature
–25
°
C to 65
°
C
Safety standards
UL508, CSA22.2
EMC directives
EN50081-2, EN50082-2
Mounting
DIN 35-mm track
Weight
Approx. 210 g
Item
Specification
Model
GT1-TS04T
GT1-TS04P
Input type
R, S, K, J, T, B, L:
Switching possible
Pt100, JPt100:
Switching possible
Accuracy
(The larger of
±
0.3% of the
displayed value or
±
1
°
C. See
note.)
±
1 digit max.
When the range is –200.0 to
650.0: (The larger of
±
0.3% of
the indicated value or 0.8
°
C)
±
1 digit max.
When the range is –200.0 to
200.0: (The larger of
±
0.3% of
the indicated value or 0.5
°
C)
±
1 digit max.
Conversion cycle
250 ms / 4 points
Temperature conver-
sion data
Binary data (4-digit Hex.)
Isolation method
Photocoupler isolation between inputs and communications
lines
Photocoupler isolation between each temperature input sig-
nal
Содержание DRT1-COM
Страница 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Страница 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xvi EC Directives 6 3 Keep DeviceNet communications cables as short as possible and ground to 100 Ω min ...
Страница 232: ...Authorized Distributor Cat No W348 E1 05 Note Specifications subject to change without notice Printed in Japan ...
Страница 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...