139
Analog Output Units
Section 5-2
7.
Select the new setting and click OK.
The output range will be set and the window for step 6 will appear again.
8.
To change other output ranges, repeat steps 6 and 7.
9.
When all the required output ranges have been changed, click OK in the
Edit Unit Parameters window of the Analog Output Unit. The Edit Device
Parameters window for the Communications Unit will appear again.
10. To make the settings for other I/O Units, repeat steps 5 to 9.
11. From the Edit Device Parameters window of the Communications Unit,
click Write to Device.
The specified output range and output for communications errors will be
set for the Analog Output Unit. At this stage, however, the setting is not en-
abled.
Output Range
output for communications errors (Error Output)