Section 3-7
+*
Configuring Set & Reset
Output Patterns
Enabling/Disabling Rate
Ranges
After you have configured Rate Ranges, as described above, every Rate Range
can be enabled or disabled. If a Rate Range is disabled (by default) no action will
be taken when the Rate Range becomes active. If a Rate Range is enabled the
corresponding Output Set & Reset Patterns are applied to the Unit Output Pattern
when that Range becomes active. To Enable/Disable Rate Ranges of Counters
refer to the following.
16
CNT1:
CNT2:
CNT3:
CNT4:
Rate Range 0:
m+44
m+89
m+134
m+179
15 14 13 12 11 10 9
8
7
6
5
4 O3 O2 O1 O0
m+45
m+90
m+135
m+180
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Output Set Pattern
Rate Range 0
m+46
m+91
m+136
m+181
15 14 13 12 11 10 9
8
7
6
5
4 O3 O2 O1 O0
m+47
m+92
m+137
m+182
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Output Reset Pattern
Rate Range 0
CNT1:
CNT2:
CNT3:
CNT4:
Rate Range 1:
m+52
m+97
m+142
m+187
15 14 13 12 11 10 9
8
7
6
5
4
4 O3 O2 O1 O0
m+53
m+98
m+143
m+188
31 30 29 28 27 26 25 24 23 22 21 20
16
Output Set Pattern
Rate Range 1
m+54
m+99
m+144
m+189
15 14 13 12 11 10 9
8
7
6
5
4 O3 O2 O1 O0
m+55
m+100
m+145
m+190
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
Output Reset Pattern
Rate Range 1
In the Set and Reset Patterns the Outputs are represented by:
= Digital Outputs 0-3
(corresponding with Physical Digital Outputs O0, O1, O2 and O3)
= Soft Outputs 4-31
If the Rate Value is within the Rate Range Limits:
(Lower Rate Range Limit
≤
Rate Value
≤
Upper Rate Range Limit)
Output Set Pattern:
Output Reset Pattern:
0 = No Change
1 = Set Output
0 = No Change
1 = Reset Output
Set/Reset actions as defined in the Output Set & Reset Pattern to control the Outputs, overrule
the Unit Output Pattern for the corresponding Outputs.
19 18 17
16
19 18 17
16
19 18 17
19 18 17
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
CNT1:
CNT2:
CNT3:
CNT4:
m+56
m+101
m+146
m+191
Rate Range 0 Enable Data:
0 = Rate Range 0 Disabled
1 = Rate Range 0 Enabled
Rate Range 1 Enable Data:
0 = Rate Range 1 Disabled
1 = Rate Range 1 Enabled
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
W902-E2-03.book Seite 87 Donnerstag, 7. Oktober 2004 2:06 14
Содержание CS1W-CT021
Страница 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Страница 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Страница 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Страница 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Страница 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Страница 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Страница 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...