K#*2'5-H#%+&"#>#*'
Section 6-2
$(+
Range Data Counters 1 and 2
Transfer the DM-settings to the High-speed Counter Unit by restarting the Unit.
:DM-word
(The hyphen “-“ indicates that the contents of the corresponding digit is
irrelevant and the value does not care)
General DM-Settings:
D 20000 (= m)
-
1
0
0
Logically AND Counter Output Patterns (=1), Range Mode (=0)
D 20010 (= m+10)
1
0
0
0
Output Pulse Duration for Digital Output O0 1000 ms (=1000
(BCD)
)
D 20017 (= m+17)
0
1
1
1
Counter 1 (=01), Digital Input I0 Function 11 (=11
(BCD)
)
D 20018 (= m+18)
0
2
0
5
Counter 2 (=02), Digital Input I1 Function 05 (=05
(BCD)
)
Counter 1 DM-settings:
D 20030 (= m+30)
-
-
-
0
Circular Counter (=0)
D 20064 (= m+64)
-
-
0
2
Total number of Ranges is 2 (=02
(BCD)
)
D 20065 (= m+65)
-
-
-
1
Memory Area is DM (=1)
D 20066 (= m+66)
0
5
0
0
D 20067 (= m+67)
-
-
-
0
Indirect Address is D00500 (=00500
(BCD)
)
Counter 2 DM-settings:
D 20075 (= m+75)
-
-
-
0
Circular Counter (=0)
D 20109 (= m+109)
-
-
0
1
Total number of Ranges is 1 (=01
(BCD)
)
D 20110 (= m+110)
-
-
-
1
Memory Area is DM (=1)
D 20111 (= m+111)
0
6
0
0
D 20112 (= m+112)
-
-
-
0
Indirect Address is D00600 (=00600
(BCD)
)
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Range 0 settings of Counter 1 (in DM):
D 00500
0
F
A
0
D 00501
0
0
0
0
Lower Range Limit is 4000 (=00000FA0
H
)
D 00502
1
3
2
4
D 00503
0
0
0
0
Upper Range Limit is 4900 (=00001324
H
)
D 00504
0
0
0
1
D 00505
0
0
0
0
Output Pattern: Digital Output O0 is ON (=00000001
H
)
Range 1 settings of Counter 1 (in DM):
D 00506
1
3
E
C
D 00507
0
0
0
0
Lower Range Limit is 5100 (=000013EC
H
)
D 00508
1
7
7
0
D 00509
0
0
0
0
Upper Range Limit is 6000 (=00001770
H
)
D 00510
0
0
0
1
D 00511
0
0
0
0
Output Pattern: Digital Output O0 is ON (=00000001
H
)
Range 0 settings of Counter 2:
D 00600
0
B
B
8
D 00601
0
0
0
0
Lower Range Limit is 3000 (=00000BB8
H
)
D 00602
0
D
A
C
D 00603
0
0
0
0
Upper Range Limit is 3500 (=00000DAC
H
)
D 00604
0
0
0
1
Output Pattern: Digital Output O0 is ON (=00000001
H
)
D 00605
0
0
0
0
W902-E2-03.book Seite 158 Donnerstag, 7. Oktober 2004 2:06 14
Содержание CS1W-CT021
Страница 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Страница 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Страница 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Страница 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Страница 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Страница 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Страница 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...