0)>4%"(+)*-?('5-0LMMNI0CMLO
Appendix A
Item
C200H-CT021
CS1W-CT021/CT041
Number of
Ranges
16 per Unit
32 per Counter (Unit in Range Mode)
Number of CV’s Not available
32 per Counter (Unit in Comparison Mode)
IORD/IOWR
Only limited IORD/IOWR-support, not able
to change Unit data at run-time
Full IORD/IOWR-support to change Unit data at
run-time
Interrupts
Not available
Inputs and Outputs can be configured to
generate Interrupts to the CS1-PLC
Resetting
Software Reset Bit, Digital Input, Z-signal
Software Reset Bit, Digital Input, Z-signal
Output State
Control
Not available
In case the PLC-CPU operating mode is
changed (RUN/MONITOR
→
PROGRAM), at I/
O Bus errors and at Overflow/Underflow the
state of the Outputs can configured to:
continue automatic updating, freeze Outputs or
predefine Output states
Noise Filter
Not available
A Noise Filter can be configured for the Counter
Inputs (10, 50 or 500 kHz) and for the Digital
Inputs (10 or 50 kHz).
Programmable
Pulse Outputs
Only available as Programmable Pulse
Duration (0 to 99.99 s) in Preset Mode
Every Digital Output can be configured to have a
Turn ON Delay (1 to 9999 ms), to have a Pulse
Duration (1 to 9999 ms) or to have a combination
of both
Rate
Measurement
Not available
For every Counter Rate Measurement can be
enabled. The Rate of incoming pulses is
measured for a predefined Time-Window (1-
9999 ms) and available from the Rate History
Log File inside the Unit. Additionally for every
Counter two Rate Ranges can be configured to
control the Outputs according to the measured
rate.
Hysteresis
Not available
To prevent Outputs switching ON and OFF due
to unwanted oscillations of an encoder being
around Range Limits or Comparison Values, an
Hysteresis (1-255 counts) can be configured.
Error Log
Function
30 error records
30 error records
W902-E2-03.book Seite 174 Donnerstag, 7. Oktober 2004 2:06 14
Содержание CS1W-CT021
Страница 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Страница 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Страница 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Страница 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Страница 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Страница 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Страница 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...