Section 3-7
+(
Configuring Rate
Measurement
Rate Measurement can be configured by setting the Time-Window between 1 ms
and 9999 ms (BCD). By default (=0) the Counters are configured to have no Rate
Measurement.
Rate Ranges
Besides the capability to measure (positive and negative) Rate Values for every
Counter two Rate Ranges (Rate Range 0 and 1) can be configured. The Rate
Ranges offer you the opportunity to undertake specific action (i.e. control the Unit
Output Pattern) when the measured Rate Values have entered a Rate Range.
Rate Ranges can represent Frequency Ranges or Rotational Speed Ranges,
making it possible to undertake action at (too high or too low Alarm) Frequencies
or Rotational Speeds.
The Data of every Rate Range is contained by 4 double words:
•
Lower Rate Range Limit, specifying the Lower Rate Limit of the Rate Range
•
Upper Rate Range Limit, specifying the Upper Rate Limit of the Rate Range
•
Output Set Pattern, specifying which Outputs must be Set if the measured
Rate Value is within the Lower- and Upper Rate Range Limits
•
Output Reset Pattern, specifying which Outputs must be Reset if the meas-
ured Rate Value is within the Lower- and Upper Rate Range Limits
The Upper Rate Range Limit must be greater than the Lower Rate Range Limit.
The Unit will generate an error if the Upper Rate Range Limit
≤
Lower Rate Range
Limit (refer to 5-2
for more details). Every Rate Range can be ena-
CNT1:
CNT1:
CNT1:
CNT1:
m+39
m+84
m+129
m+174
Time-Window:
0000
(BCD)
= No Rate Measurement
0001-9999
(BCD)
= Time-Window in milliseconds
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Time
Rate Value
Alarm-Area
Rate Range 0 Upper Limit
Rate Range 0 Lower Limit
Rate Range 1 Upper Limit
Rate Range 1 Lower Limit
Time-Window
Alarm-Area
Time
W902-E2-03.book Seite 85 Donnerstag, 7. Oktober 2004 2:06 14
Содержание CS1W-CT021
Страница 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Страница 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Страница 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Страница 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Страница 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Страница 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Страница 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...