710.1760.00.04-05
22/05/2014
33
No.
Device
status
Alarm
code
Alarm de-
scription
Possible cause
Recommended remedy
Fault
rectification (*)
4
Pump, fan
and
compressor
are working
HA
High liquid
temperature
alarm
Ambient temperature too
high
Decrease ambient tempera-
ture, increasing ventilation of
the room, removing heat
sources or repairing the unit
from the direct rays of sun
A
Dirty condenser
Clean the condenser as
described in maintenance
Fan is not working fine or
the sense of rotation is not
correct
Check fuse of the fan (if
presents), and right rotation
Required cooling capacity is
higher than nominal
Decrease the required cooling
capacity
Unit low on refrigerant
Check liquid sight glass (if
present) and in case contact
service
Air filter dirty (only for unity
with this kind of option)
Dismount the filter from the
unit and clean it with air or
with water
LA
Low liquid
temperature
Ambient temperature too
low is decreasing liquid
temperature
The unit have to work in
ambient condition as specified
in this manual
P2
Sensor SA
defective
Probe can be defective or
not well connected
Check connection and in case
change probe
(*)
A
After fault rectification, system is automatically restored to standard setting –
M
Alarm function restored by settings made on
the control unit, procedure as described below.
HOW TO VISUALIZE A WARNING/ALARM EVENT (CONTROLLER TYPE “D”)
CONTROLLER Type “D”
(CHW 11 to CHW 36; CHG 08)
The LED warning alarm on
shows that an alarm is taking place.
To see which kind of alarm, the max temperature (minimum) and the length, act as follow:
1)
Press one of the two buttons
or
the display will show “
Hi
” (high temperature alarm) or
“
Lo
“ (low temperature alarm) followed by
Max. temperature
or
Min. temperature
.
HOW TO RESET AN ALARM EVENT
1)
Press the button
or
, the display shows “
Hi
” (high temperature alarm) or “
Lo
” (low
temperature alarm).
2)
Keep button
pressed
1)
The display shows: “
rST
”, which after 2 sec starts lightening, to show that the values have
been cancelled
CONTROLLER TYPE “B” (CHW 29 TO CHW 149; CHO 29 TO CHO 149; CHG 24 TO CHG 100)
CONTROLLER TYPE “E”, (CHW 162 TO CHW 602; CHG 140 TO CHG 180)
No.
Device
status
Alarm
code
Alarm de-
scription
Possible cause
Recommended remedy
Restore (*)
1
Fan, Com-
pressor and
pump are
not working
OFF
Unit is in Off by
remote ON/OFF
Remote ON/OFF contact is
open or internal bridge re-
moved
Check bridge ROO and close
the contact
A
z
Unit in stand by
The unit is energized but not
switched on
Follow procedure to start up the
unit using button on controller
A
A08
Flow switch
alarm
Liquid flow too low
Check right rotation of the
pump and possible obstruction
on liquid circuit
A
becomes
M
after 1
events in 1
hour
Liquid in the tank too low
Fill the tank
Содержание CHG 08
Страница 39: ...710 1760 00 04 05 22 05 2014 39 1 1 1 CHW CHO CHG chiller CHW CHO CHG 1 2 CHW CHO CHG CHW CHO CHG CHW CHO CHG 2...
Страница 40: ...710 1760 00 04 05 22 05 2014 40 CHW 20 25 CHO 10 cST CHG 20 25 5 EN 60204 EN 378 2...
Страница 41: ...710 1760 00 04 05 22 05 2014 41 HFC CE 842 2006 3 3 1 3 2 C CND EVA HP LP...
Страница 42: ...710 1760 00 04 05 22 05 2014 42 MHP MLP PV R V a 2 5 b VE 2 5 MOP IAF 3 3 MF P...
Страница 43: ...710 1760 00 04 05 22 05 2014 43 BP BPM CAA EV 1 1 VNR FL LVE RA TD VNR EV 1 2 3...
Страница 44: ...710 1760 00 04 05 22 05 2014 44 1 2 3 4 5 6 7 3 4 ALR...
Страница 48: ...710 1760 00 04 05 22 05 2014 48 CHW 97 CHW 3652 4 2 4 3 5 50 C 12 6 5 2 5 5 1 2 C 40 C 2 C 40 C...
Страница 50: ...710 1760 00 04 05 22 05 2014 50 25 1 60 CHO A B C D E Abb 1 TN C 230 1 1 N PE AC 400 3 3 PEN AC PEN...
Страница 65: ...710 1760 00 04 05 22 05 2014 65 CHW 682 CHW 3652 CHG 225 CHG 365 6 4 1 2 0 0 5 2 1...
Страница 67: ...710 1760 00 04 05 22 05 2014 67 5 6 8 9 10 3 20 15...
Страница 68: ...710 1760 00 04 05 22 05 2014 68 9 1 A CHW 11 CHW 36 CHG 08 1 OFF A OFF LA2 P1 SL HA 2 A 3 LA2 2 A CA 4 HA A...