710.1760.00.04-05
22/05/2014
12
* Remove the pallet (if present).
* Place the chiller in the desired location.
* Remove the operating manual, accessories and key from the chiller.
CHW 97 - CHW 3652
4.2
DISPOSAL OF PACKAGING MATERIALS
We recommend that you keep the original packaging for the chiller in case it has to be transported to an-
other location or sent to a service centre. In any case, the waste packaging material must be deposited
with the responsible waste disposal companies.
4.3
STORAGE
The chiller must be stored in rooms protected from weather-related influences. These rooms must be dry
and have a temperature range of b5 and +50°C.
If the chiller is stored for longer than 12 months, please contact the manufacture before
starting up the chiller again to check the condition of the machine parts, particularly the elec-
trical components.
See Chapter 6.5.2 (Temporary decommissioning).
5.
LOCATION AND INSTALLATION
5.1
CHOOSING A LOCATION
Install the chiller in a protected dry area, free of fumes, dust or flammable vapours that is not
subject to an explosive hazard. The atmosphere must be free of any constituents that may im-
pair the proper functioning of the chiller.
A suitable area must be found in which a temperature of not less than +2°C and definitely not more than
+40°C can be guaranteed at any time of the year while the machine is operating. If you wish to operate
the chiller at ambient temperatures of less than +2°C or more than +40°C, please contact the manufac-
turer in connection with the necessary adaptations.
We recommend that appropriate ventilation should be provided. Operating the chiller heats up the area in
which it is installed. This applies particularly to chillers with a standard air-cooled condenser.
So as not to impair the cooling capacity of the chiller, we recommend protecting it against direct sunlight.
You should avoid connecting the axial ventilators to air ducts as they do not have sufficient compression.
Higher ambient temperatures than those given as a reference value in the data sheet reduce the cooling
capacity.
The chiller should be installed on a horizontal and level surface that is capable of absorbing the compres-
sive load of the chiller. Larger chillers have holes at the ends of the supporting rails so that they can be
fastened to the floor.
When the chiller is installed outside, it should be protected against any atmospheric influences. Please
consult the manufacturer for further details.
Содержание CHG 08
Страница 39: ...710 1760 00 04 05 22 05 2014 39 1 1 1 CHW CHO CHG chiller CHW CHO CHG 1 2 CHW CHO CHG CHW CHO CHG CHW CHO CHG 2...
Страница 40: ...710 1760 00 04 05 22 05 2014 40 CHW 20 25 CHO 10 cST CHG 20 25 5 EN 60204 EN 378 2...
Страница 41: ...710 1760 00 04 05 22 05 2014 41 HFC CE 842 2006 3 3 1 3 2 C CND EVA HP LP...
Страница 42: ...710 1760 00 04 05 22 05 2014 42 MHP MLP PV R V a 2 5 b VE 2 5 MOP IAF 3 3 MF P...
Страница 43: ...710 1760 00 04 05 22 05 2014 43 BP BPM CAA EV 1 1 VNR FL LVE RA TD VNR EV 1 2 3...
Страница 44: ...710 1760 00 04 05 22 05 2014 44 1 2 3 4 5 6 7 3 4 ALR...
Страница 48: ...710 1760 00 04 05 22 05 2014 48 CHW 97 CHW 3652 4 2 4 3 5 50 C 12 6 5 2 5 5 1 2 C 40 C 2 C 40 C...
Страница 50: ...710 1760 00 04 05 22 05 2014 50 25 1 60 CHO A B C D E Abb 1 TN C 230 1 1 N PE AC 400 3 3 PEN AC PEN...
Страница 65: ...710 1760 00 04 05 22 05 2014 65 CHW 682 CHW 3652 CHG 225 CHG 365 6 4 1 2 0 0 5 2 1...
Страница 67: ...710 1760 00 04 05 22 05 2014 67 5 6 8 9 10 3 20 15...
Страница 68: ...710 1760 00 04 05 22 05 2014 68 9 1 A CHW 11 CHW 36 CHG 08 1 OFF A OFF LA2 P1 SL HA 2 A 3 LA2 2 A CA 4 HA A...