Heating circuit setpoints
Setpoint
Description
Adjustment range
Factory
setting
HC1...HC3 max
temperature
Maximum flow temperature for heating
circuit 1...3
0–90 °C
60 °C
HC1...3 min temperature
Minimum flow temperature for heating
circuit 1...3
0–90 °C
5 °C
4.6.2 Backup device settings: options for backup heater
These options apply only to configurations where the electric immersion
heater is not used in parallel with the heat pump.
In this view, you can specify how the electric immersion heater will be used in case of
a compressor malfunction. If the compressor’s hot gas temperature does not exceed
50 °C within a specified time, the electric immersion heater will be switched on.
● To allow the heater to be used as a backup heat source, check the
In use
checkbox.
● To specify the delay for switching on the heater, tap on the
Backup device start
time
field. The value is given in hours.
4.6.3 Partial power settings
These options apply only to configurations where the electric immersion
heater is used in parallel with the heat pump.
In this view, you can specify the delay before supplementary heating is switched on.
The heat pump’s electric immersion heater will operate in parallel with the compressor.
To specify the delay, tap on the
Heating time before extra heat
field. The value is
given in minutes.
4.6.4 Summer functions
The summer functions view is used to specify the period during which some or all
heating circuit pumps are switched off to save energy. To prevent the pumps from
seizing up, the pumps will be run for 30 seconds once a week.
M8011 2204EN
39 (70)