Problem
Cause
Solution
In summer, the flow temperature
sensor reading is higher than the
value provided by the heating
curve. This is caused by a
temperature increase in the
heating circuit.
No action required.
The demand for heating is high
due to, for example, a very low
outdoor temperature or, during the
first year, heat required for drying
out the building’s structures.
No action required.
The compressor starts frequently
or stays on for long periods of
time.
Insufficient refrigerant charge.
Check whether there are bubbles
in the sight glass even after
some minutes of use. Contact a
refrigeration or appliance service.
*This type of damage is not covered by the warranty.
5.3 Alarms
Active alarms
When there are active alarms in the system, a bell icon will be displayed in the main
view.
To view active alarms, tap on the bell icon.
Alerts ver. 1
The
Alerts
view shows a list of active alarms in the system.
To acknowledge all active alarms, tap on the bell icon with
strikethrough.
To access the Alarm history view, tap on the recycling button.
Alarm history
To access the heat pump’s
alarm history
, tap on the menu button in
the main view and tap on the
Alarm history
button.
Alternatively, tap on the recycling button in the
Alerts
view.
M8011 2204EN
45 (70)
Содержание VSi 6-14
Страница 1: ...M8011 2204EN 25 January 2022 Installation and operation manual VSi 6 14 VMi 6 17 ss Control...
Страница 2: ......
Страница 59: ...Dimensional drawings VSi 10VS14_2 VSI 1 ver 1 10VS14_2 VSI 2 ver 1 M8011 2204EN 57 70...
Страница 60: ...Dimensional drawings VMi 10VMI141_2 VMI 1 ver 1 10VMI141_2 VMI 2 ver 1 58 70 M8011 2204EN...
Страница 73: ......