4.29 O
2
trim control operating mode (WD200)
Select the suitable O
2
trim control operating mode as follows:
Params. & Display
O2Contr/Guard
FuelSettings
OptgMode
auto deact
man deact
O2 Limiter
O2 Control
conAutoDeac
O
2
trim control operating modes
man deact
Use this setting when creating O
2
ratio curve.
Both
O2Limiter
and
O2Control
are deactivated. Burner operates according to
parameterized ratio curves.
O2 Limiter
Only
O2Limiter
is active. Oxygen sensor must have reached its operating
temperature. If not, start-up will be prevented. If oxygen sensor or O
2
module
causes a failure during burner operation, burner stops, tries to restart or lockout
occurs.
O2 Control
Both
O2Limiter
and
O2Control
are active. Oxygen sensor must have reached its
operating temperature. If not, start-up will be prevented. If oxygen sensor or O
2
module causes a failure during burner operation, burner stops, tries to restart or
lockout occurs.
conAutoDeac
Use this setting during normal operation.
Both
O2Limiter
and
O2Control
are active. Burner starts, though oxygen sensor
has not reached its operating temperature. Burner operates along parameterized
ratio curves. When oxygen sensor has reached its operating temperature and
sensor test has been successfully completed, both
O2Limiter
and
O2Control
are
active. If oxygen sensor or O
2
module cause failure during burner operation, both
O2Limiter
and
O2Control
are deactivated. Burner operates along parameterized
ratio curves. O
2
trim control status in operating and display unit is automatically
set to
auto deact
, and error code is displayed. Error code is maintained until O
2
trim control is manually deactivated or activated.
auto deact
O
2
trim control has automatically been deactivated and burner operates along
parameterized ratio curves.
Do not select this option!
If O
2
trim has been automatically deactivated, then you can reactivate it
from:
Operation
↵
O2Ctrl Activate
↵
Activate
↵.
4.30 O
2
trim control load limitation (WD200)
Select
O2CtrlThreshold
from the operating and display unit menu as follows:
78 (129)
M5178 1647EN
Содержание GKP-350 M
Страница 2: ......
Страница 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Страница 6: ...4 129 M5178 1647EN...
Страница 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Страница 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Страница 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Страница 132: ...130 129 M5178 1647EN...
Страница 133: ......