![Oilon GKP-350 M Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/oilon/gkp-350-m/gkp-350-m_operation-and-maintenance-manual_3563516051.webp)
4. Slowly turn the gas pressure switch towards its minimum setting until the burner
shuts off. The pressure switch is now correctly configured.
5. Reset the error.
6. Decrease gas pressure to normal value. Check combustion values.
To adjust gas pressure switch, min.
Burner size
Factory setting mbar
Factory setting PSI
450 M
20
0.29
Scale precision ±15 %
1. Open switch transparent cover.
2. Set burner to full capacity.
3. Set the switch to trigger on a 20–40 % lower pressure than the gas inlet pressure to
burner.
4. Close cover.
If gas pressure switch triggers a temporary burner shutdown during burner start-up or
during operation, it has to be set on lower pressure.
Gas pressure switch, gas valve proving
Gas valve leaking is tested by using a pressure switch. Switch adjustment according to
previous instructions.
4.11 Setting variable speed module parameters
Variable speed module (VSM) is an optional accessory that is connected to burner
control through LSB bus. Electrical connections (sensors, mA/V messages etc.) to
burner control are made according to electrical connections.
VSM module provides 0/4-20mA or 0-10V setpoint output for frequency converter. In
addition there is a changeover contact in the burner to get frequency converter started.
VSM basic settings are adjusted with DIP switches and parameter settings with PC
application (LSB remote).
DIP switches are located on the module cover. Following tables show factory settings
underlined:
DIP1
Setting
0
CAN terminating resistor deactivated
1
CAN terminating resistor activated
DIP 2–3, product family
DIP2
DIP3
LSB family
0
0
1
0
1
2
1
0
3
1
1
4
M5178 1647EN
49 (129)
Содержание GKP-350 M
Страница 2: ......
Страница 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Страница 6: ...4 129 M5178 1647EN...
Страница 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Страница 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Страница 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Страница 132: ...130 129 M5178 1647EN...
Страница 133: ......