Removing regulating unit motor
D033674 ver. 1
Pos.
Item
Pos.
Item
1
Servomotor
4
Shaft coupling
2
Servomotor fixing screw
5
Shaft coupling aligning screw
3
Servomotor shaft and aligning level
6
Shaft coupling clamping screw
1. Disconnect the cables according to the instructions.
2. Loosen the clamping and aligning screw of the shaft coupling; shaft coupling stays
on regulator valve shaft.
3. Detach the servomotor fixing screws and remove the servomotor.
4. Fix the new servomotor to the shaft coupling.
5. Check that the shaft coupling aligning screw is at servomotor shaft level.
6. Check that the shaft coupling clamping screw is tightened.
7. Place the new servomotor.
8. Tighten the servomotor fixing screws.
9. Connect the cables according to the instructions.
Addressing servomotor
The address is determined by connector position (X32-X34). Determination can be
changed with a PC tool.