O
2
min. value surface is verified by throttling air and measuring CO level at the
same time.
4. When desired oxygen level is reached, accept the value by pressing
Enter
. Exit by
pressing
Esc
. Repeat for each curve point.
Start setting O
2
ratio control after O
2
min. value control is set.
4.28 Setting O
2
trim control (WD200)
O
2
min. value
O2Control
must be set first.
It is important that environmental conditions do not change when setting O
2
trim
control.
If the curves are changed later, adjust also O
2
trim control.
The first curve point from which O
2
trim control begins is preset at curve point 2. That
is the first point to be set for O
2
trim control. At this point burner control calculates low
capacity settings for O
2
trim control. At lower capacity burner operates according to
ratio curve, without O
2
trim control.
1. Select
O2 Control
from the following menu level:
Params. & Display
O2Contr/Guard
Fuel Settings
O2 Control
2. The first O
2
trim control point is curve point 2.
At lower capacity burner operates according to ratio curve.
Confirm the selection by pressing
Enter
. The burner runs to point 2 capacity.
Point2 ver. 3
3. The display changes. The second line
O2ratioCon
shows current residual oxygen
level. Wait until the level stabilizes, and corresponds with ratio curve level. The
burner control uses this level when calculating O
2
trim control settings.
Confirm the selection by pressing
Enter
.
76 (129)
M5178 1647EN
Содержание GKP-350 M
Страница 2: ......
Страница 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Страница 6: ...4 129 M5178 1647EN...
Страница 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Страница 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Страница 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Страница 132: ...130 129 M5178 1647EN...
Страница 133: ......