4.33 Setting capacity controller parameters
Standard parameter setting
Capacity controller contains 5 standard parameter settings that can be selected and
activated, depending on characteristics of controlled process.
Params. &
Display
Load- Controller
Controller-
Param
ContrlParam-
List
Standard-
Param
Adaption
very fast
fast
normal
slow
very slow
Standard parameters are listed in the following table:
P [%]
I [s]
D [s]
Very fast
42.5
68
12
Fast
14.5
77
14
Normal
6.4
136
24
Slow
4.7
250
44
Very slow
3.4
273
48
P = Proportional band
I = Integral action time
D = Derivative action time
Setting parameters individually
PID parameters can also be set individually according to the following value range:
●
P-Part (Xp)
2…500% of the measurement range
●
I-Part (Tn)
0…2000s, 0=no I part
●
D-Part (Tv)
0…1000s, 0=no D part
Params. & Display
LoadController
ControllerParam
ContrlParamList
M5178 1647EN
81 (129)
Содержание GKP-350 M
Страница 2: ......
Страница 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Страница 6: ...4 129 M5178 1647EN...
Страница 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Страница 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Страница 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Страница 132: ...130 129 M5178 1647EN...
Страница 133: ......