LoadLimits
MinLoadGas.
Minimum load
"Low fire" (gas)
MaxLoadGas
Maximum load
"High fire" (gas)
On user level, maximum load can be set individually as follows:
Description
Operation
User Maxload
User MaxLoadMod
Maximum load on
modulating burner
4.27 O
2
min. value control (WD200)
O
2
ratio control can be set after setting the ratio curve.
Ratio curve air amount should be approx. 1 % higher than O
2
ratio
control, so that environmental changes do not set residual oxygen level
below O
2
trim control level.
Ratio curve should be as smooth as possible. If the curve has sharp breakpoints, set
one additional point to smooth the curve. Even ratio curve improves O
2
ratio control.
In dual-fuel burners, set the O
2
ratio control individually for both fuels, and they are not
correlating.
Start O
2
ratio curve by setting O
2
min. value control.
O
2
min. value control
When setting for the first time
O2 monitor
should be deactivated with
man deact
.
Params. & Display
O2Contr/Guard
FuelSettings
OptgMode
man deact
Set O
2
min. value control as low as possible to ensure a high availability. O
2
min. value
is between the permanently non-hazardous range and the potentially hazardous range.
O
2
ratio curve is set at lowest 0.5 %–1 % above O
2
min. value, so during normal burner
operation this level should not be reached.
74 (129)
M5178 1647EN
Содержание GKP-350 M
Страница 2: ......
Страница 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Страница 6: ...4 129 M5178 1647EN...
Страница 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Страница 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Страница 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Страница 132: ...130 129 M5178 1647EN...
Страница 133: ......