TUF-2000F User Manual
32
AOa
(cr)
Output current ‘a’ mA at the AO output
terminal.
AOa
(cr)(lf)Note 6
BA1(cr)
Return the resistance for T1
±d.ddddddE±dd(cr)(lf)
BA2(cr)
Return the resistance for T2
±d.ddddddE±dd(cr)(lf)
BA3(cr)
Return current value of AI3 (0~20mA)
±d.ddddddE±dd(cr)(lf)
BA4(cr)
Return current value of AI4 (0~20mA)
±d.ddddddE±dd(cr)(lf)
BA5(cr)
Return current value of AI5 (0~20mA)
±d.ddddddE±dd(cr)(lf)
AI1(cr)
Return temperature at T1 input
±d.ddddddE±dd(cr)(lf)
AI2(cr)
Return temperature at T2 input
±d.ddddddE±dd(cr)(lf)
AI3(cr)
Return temperature /pressure value of
AI
3
±d.ddddddE±dd(cr)(lf)
AI4(cr)
Return temperature /pressure value of AI4 ±d.ddddddE±dd(cr)(lf)
AI5(cr)
Return temperature /pressure value of AI5 ±d.ddddddE±dd(cr)(lf)
ESN(cr)
Return the ESN (electronic serial number)
of the flow meter
ddddddd
(cr)(lf) note 7
N
Prefix of an IDN-addressing-based
networking, The IDN address is byte,
range 0-253
Note
8
W
Prefix of an IDN-addressing-based
networking, The IDN address is word,
range 0-65535
Note
8
P
Prefix of any commands for returns with
check-sum
&
Commands connector to make a
compounding command in one line.
Result commands should not exceed
253 bytes long.
RING(cr)(lf)
Handshaking request from a modem
ATA(CR)(lf)
OK(cr)
Acknowledgement from a modem.
No action
Handshaking from the flow meter to
modem.
AT(CR)(LF)
GA(cr)
Special command for GSM network.
note
9
GB(cr)
Special command for GSM network.
note
9
GC(cr)
Special command for GSM network
note
9
Note:
0.
(
cr
)
stand for carriage return, its ASCII value is 0DH. (lf) stand for line feed, its ASCII value
is 0AH.
1
.
d stand for a digit number of 0~9, 0 is expressed as +0.00