TUF-2000F User Manual
30
3597-3598
2
Time duration when off
LONG
In seconds
3599-3600
2
Corrected lost flow when
off
REAL4
In cubic meters
3601
1
Power-on second and
minute
BCD
Second in low byte, minute in high
3602
1
Power-on hour and day
BCD
Hour in low byte, day in high
3603
1
Power-on month and
year
BCD
Month in low byte, year in high
3604
1
Power-on error code
BIT
B15 stand for corrected lost flow.
3605
1
Power-off second and
minute
BCD
Second in low byte, minute in high
3606
1
Power-off hour and day
BCD
Hour in low byte, day in high
3607
1
Power-off month and
year
BCD
Month in low byte, year in high
3608
1
Power-off error code
BIT
B15 stand for corrected lost flow
3609-3610
2
Flow rate when power
on
REAL4
Flow rate after 60 seconds when
power on
3611-3612
2
Flow rate when power
off
REAL4
3613-3614
2
Time duration when off
LONG
In seconds
1
3615-3616
2
Corrected lost flow when
off
REAL4
In cubic meters
。。。。
。。。。。。。。。
。。。
。。。。。。 。。。。。。。。。。。。。。。。。。。。
31
3825-3840
16
The
32
nd
data block
5.2 The FUJI extended communication protocol
TUF-2000F is compatible with the TUF7-FUJI extended communication protocol which used
in our previous Version7 ultrasonic flow meters. This protocol is a set of basic commands that
are in ASCII format, ending with a carriage return (CR) and line feed (LF), For most of the
commands, The line feed (LF) should be better omitted for fast responding.
Command
Meaning
Data format
DQD(cr)
note 0
Returns flow rate per day
±d.ddddddE±dd(cr)
note 1
DQH(cr)
Return flow rate per hour
±d.ddddddE±dd(cr)
DQM(cr)
Return flow rate per minute
±d.ddddddE±dd(cr)
DQS(cr)
Return flow rate per second
±d.ddddddE±dd(cr)
DV(cr)
Return fluid velocity
±d.ddddddE±dd(cr)
DI+(cr)
Return positive totalizer
±dddddddE±d(cr)
note 2
DI-(cr)
Return negative totalizer
±dddddddE±d(cr)