PROGRAMMING GUIDE

ACS-30 System

Содержание RAYCHEM ACS-30

Страница 1: ...nVent com 1 Raychem AR H58692 ACS30UIT2Programming EN 1805 PROGRAMMING GUIDE ACS 30 System...

Страница 2: ...nVent com 2 Raychem AR H58692 ACS30UIT2Programming EN 1805...

Страница 3: ...EADER 14 1 10 2 MAIN MENU WINDOW 14 2 Section 2 System Configuration 17 2 1 Initializing the System 17 2 1 1 SETTING UP GENERAL SYSTEM PARAMETERS 18 2 1 2 SETTING TIME AND DATE 19 2 1 3 SCANNING THE N...

Страница 4: ...ROL 98 3 8 2 TEMP CONTROL AMBIENT TEMPERATURE CONTROL 102 3 8 3 TEMP CONTROL BRACKETED AMBIENT TEMPERATURE CONTROL 105 3 8 4 TEMP CONTROL SURFACE TEMPERATURE CONTROL 109 3 9 Snow Melting Mode 113 3 9...

Страница 5: ...5 C910 485 RMM2Remote monitoringmodule ACS PCM2 5 ACS PCM2 5 ALAR M C910 SERIE S SHIFT TEST BACK ENTER STATU S ALARM OUTPU T MONIT OR CONFIG PROGR AMMAB LE SINGLE POINT HEAT T RACIN G CONTR OLLER Fig...

Страница 6: ...he heating cable circuits are located The control panels controllers should be located adjacent to circuit breaker panels and are connected in series to the ACS UIT2 with RS 485 cable 1 1 6 COMMUNICAT...

Страница 7: ...not sold to you for use only under the terms of this Agreement and nVent reserves any rights not exactly granted to you Subject to the terms and conditions of this Agreement nVent grants to you a non...

Страница 8: ...E RESULTS AND PERFORMANCE OF THE SOFTWARE IS ASSUMED BY YOU IN NO EVENT SHALL NVENT ITS AFFILIATES DIRECTORS OFFICERS SHAREHOLDERS EMPLOYEES OR OTHER REPRE SENTATIVES BE LIABLE FOR DAMAGES OF ANY KIND...

Страница 9: ...s applicable This provision applies to the ACS 30 Software acquired directly or indirectly by or on behalf of any government The ACS 30 Software is a commercial product licensed on the open market at...

Страница 10: ...ocal representative or contact nVent directly 1 6 TECHNICAL SUPPORT For technical support contact your local representative or contact nVent directly NVENT THERMAL MANAGEMENT Tel 800 545 6258 Tel 650...

Страница 11: ...nsing Constant temp Variable schedule Maintain Economy Off Circuit override through RTD or external device Greasy Waste Disposal and Temperature Maintenance XL Trace Line sensing Constant temp Variabl...

Страница 12: ...elay 5 Local RTD Fig 1 2 Simple control circuit Heating control circuits can also be connected to the dry contact output of BMS systems external monitoring devices or moisture sensing controllers for...

Страница 13: ...s may be used for control or monitoring of a heating circuit 1 LC GF Output Relay 1 Local A RTD 2 LC GF Output Relay 2 Local RTD 3 LC GF Output Relay 3 Local RTD 4 LC GF Output Relay 4 Local RTD 5 LC...

Страница 14: ...displays the following data from left to right A ID tag Hot water line 1 B ACS PCM2 5 address 01 C Relay output number 1 D Application control mode HWAT Fig 1 7 Navigational header 1 10 2 MAIN MENU W...

Страница 15: ...a floor heating application Pipe freeze Circuit has been set up for a pipe freeze protection application Fuel Oil Circuit has been set up for a fuel oil flow maintenance application Greasy waste TM C...

Страница 16: ...ts on the Main window and on the Events Alarms on the Events window When in the Main or Events windows tap on anywhere on a row for a circuit to see the Status window for that circuit Fig 1 9 Main win...

Страница 17: ...ogress Fig 2 1 Initial ACS software loading display window When the ACS UIT2 is powered on for the first time date and units will not been assigned In addition the ACS UIT2 has not yet scanned the net...

Страница 18: ...must be touched to show the circuit s alarm status IMPORTANT Using the screen saver enhances the lifetime of the screen Range 1 300 minutes Default 20 minutes Main Menu Timer Sets the number of minut...

Страница 19: ...ACS UIT2 is connected to the external ACS PCM2 5 modular power control panels C910 485 controllers and any RMMs via the RS 485 network and all circuits have been installed and commissioning tests comp...

Страница 20: ...ACS PCM2 5 Installation Instructions H58238 C910 485 Installation Instructions H58415 and RMM2 Installation Instructions H56848 for more information To set the modbus address for a C910 485 controller...

Страница 21: ...1 99 RMM2 RTD 0 9 32 41 RMM2 RTD A F 42 47 2 1 4 MAIN WINDOW After the first system scan has been completed tap the Main menu button and the main window appears Fig 2 8 Main window with one CRM board...

Страница 22: ...the ACS 30 program By default each of the five relays are numbered as the CRM number and relay number e g 1 1 1 2 1 3 1 4 and 1 5 The CRM number and relay number are a primary reference for all window...

Страница 23: ...overriding the control mode but generates alarms and enables high temperature cut out Force Off The ACS UIT2 has turned the circuit off but generates low temperature and system alarms 2 2 2 ASSIGNING...

Страница 24: ...flow maintenance with line control XL Trace 3 6 2 85 Fuel oil flow maintenance with PASC2 control XL Trace 3 6 3 90 Greasy Waste TM Greasy waste and other temperature maintenance control Variable tem...

Страница 25: ...utton is tapped again Fig 2 12 Start Stop test Copy Circuit The Copy Circuit button allows you to assign other available circuit number circuit with identical control parameters Select the circuit con...

Страница 26: ...als for this circuit then all four lines can be used to assign RTDs from elsewhere in the system However in the event of a communications or UIT failure no RTD input is available and the relay output...

Страница 27: ...16 Ambient Control or Line Monitor HWAT Mode No RTDs are required or can be used for control However RTDs can be assigned for line monitoring with temperature alarms External Device Control A controll...

Страница 28: ...WAT Timed duty cycle X Freezer Frost Heave Line slab sensor X X Floor Heating Line slab sensing X X Ext Pipe Freeze Protection Line sensing X X Ext Ambient or PASC1 X X Ext Fuel Oil Flow Maintenance L...

Страница 29: ...ircuit from ACS CRM boards or RMM2 modules To assign the additional RTDs to a circuit enter the device address and RTD number as listed under your Network Device window Fig 2 18 Assigning additional R...

Страница 30: ...10 485 measures the applied voltage so this field is not required for energy usage calculations Fig 2 21 Setup Voltage window Tapping the Voltage Field opens a voltage selection screen with choices of...

Страница 31: ...en not in demand to ensure the circuit RTD or communications have not been damaged and will be working when needed The user can select the time of day the test will be conducted Note If the circuit is...

Страница 32: ...fic circuit ID Displays the ID tag defined in Setup Circuit window Mode Displays the Control Mode selected in Setup Circuit window Alarm Reset In normal state the Alarm Reset button is grayed out If a...

Страница 33: ...ate Black Circuit is off Green Within normal range of setup parameters Red In alarm condition Orange Temperature is not within setpoint plus deadband range Blinking Red Orange A latching alarm event h...

Страница 34: ...ontrols Control Temp Max The highest temperature reported by any line RTD associated with the circuit since the last reset time Min The lowest temperature of any line RTD associated with the circuit s...

Страница 35: ...e in order store or statistically analyze the data See Appendix 5 6 for more information Different views are available and selectable by a dedicate menu Fig 2 29 Status Energy window window View selec...

Страница 36: ...Fig 2 31 Status Energy window Day selection Hourly view The daily view plots the energy consumption over the selected month year with a time interval of one day Fig 2 32 Status Energy window Daily vi...

Страница 37: ...y view The monthly view plots the energy consumption over the selected year with a time interval of one month Fig 2 35 Status Energy window Monthly view Fig 2 36 Status Energy window Year selection Mo...

Страница 38: ...st and next power cycle is displayed The power cycle test energizes the heating cable selected for 2 minutes to verify it is in working order Fig 2 38 Status Maint window The Status Maint window provi...

Страница 39: ...cending or descending order Events Press for Alarms By taping the Events heading the Events display filters events or alarms by type Time and Circuit column headings can then be used to further sort t...

Страница 40: ...nd Fault OK Ground fault returned to acceptable range Ground Fault Trip Heating cable s ground fault current has exceeded Ground Fault Trip limit for circuit and has disabled the contactor or SSR Grou...

Страница 41: ...rm condition which requires reset in the Status Circuit window 2 9 NETWORK RELAYS WINDOW The Network Relays window lists all the available output devices and relay numbers Fig 2 40 Network Relays wind...

Страница 42: ...he RS 485 network Fig 2 42 Network Maint window 2 12 NETWORK REMOVE WINDOW The Network Remove window is Level 2 password protected Once accessed it allows you to remove device addresses for ACS PCM2 5...

Страница 43: ...The ACS UIT2 can be connected to a Building Management System BMS or host computer using an RS 485 RS 232 or 10 100Base T Ethernet connection All data and setup options are accessed with communicatio...

Страница 44: ...al communication port Selection 2400 4800 9600 19200 38400 57600 Default 9600 Serial Port Mode This activates a window which allows selection of RS 232 or RS 485 ports This selects the serial communic...

Страница 45: ...ue determines how long the password remains active before it has to be re entered The password is limited to 40 characters Default Level 1 disabled New Password Enter the user defined password Save Ne...

Страница 46: ...te By clearing the event all the events and alarms history information for all circuits is lost If the program exit is chosen heating cables are no longer monitored Exit ACS UIT2 Allows user to exit A...

Страница 47: ...M Enter Maintain Deadband Fail safe Constant F H Heating cable Y2 or R2 Voltage 208 240 277 Ambient 60 F to 90 F Pipe material Metal plastic Maintain and Economy temp RTD and external device override...

Страница 48: ...ou for information necessary to maintain the hot water piping system at the desired temperature 3 2 1 ENTER SYSTEM INFORMATION Select Cable Type Select the heating cable type being used with this circ...

Страница 49: ...ffects the power output of the HWAT self regulating heating cables Enter the pipe material Fig 3 5 Select pipe type Select Setpoint Mode Select the setpoint Constant or Variable Constant will allow a...

Страница 50: ...mode Enter Temperature Setpoints Enter the temperature setpoints that you want to maintain the hot water pipe Minimum setpoint temperature 100 F Maximum setpoint temperatures are dependant upon the a...

Страница 51: ...the HWAT design wizard the Setup HWAT window appears where you can adjust the input variables established in the design wizard and enter access additional menu windows Fig 3 8 Setup HWAT window Econo...

Страница 52: ...ee Appendix 5 2 24 7 Scheduler on page 127 for more information Power Factor The factor is used to decrease or increase the final pipe temperature Increasing this value above 100 will result in a long...

Страница 53: ...arm Range 40 F 4 C to Maintain temperature Default 40 F 4 C TEMPERATURE ALARM FILTER This minimizes nuisance alarms by forcing the ACS UIT2 to verify that the alarm condition continually exists over t...

Страница 54: ...ion normally without the high temperature cut out feature Options Enable or Disable Default Enable Assigning Ground Fault Alarm and Trip Levels The Setup G F window allows you to set the alarm and tri...

Страница 55: ...perature the output is turned on Range 1 F 1 C 10 F 6 C Default 5 F 3 C FAIL SAFE The Fail Safe control button turns the power on or off to the heating cable if the circuit loses all valid RTDs When t...

Страница 56: ...to the circuit the alarm button appears then high and low temperature alarms may be set Fig 3 14 Setup Alarms window Frost Heave HIGH LINE TEMP ALARM If any RTDs assigned to a circuit measures a temp...

Страница 57: ...and the relay output is turned off If the high line temperature drops below this threshold minus the deadband the output is turned on and normal duty cycle control is resumed Range High Temperature A...

Страница 58: ...CIRCUIT VOLTAGE Voltage 120 208 240 or 277 V Standard ACS PCM2 5 panels Since the C910 485 measures line voltage this field does not appear Default 208 V ASSIGNING POWER CYCLE TEST The Setup Maint win...

Страница 59: ...maintain the system at the desired setpoint Range 60 F 16 C 110 F 43 C Default 83 F 28 C Economy Temperature optional This value represents the temperature that you want the pipe to maintain when in e...

Страница 60: ...C Default 55 F 13 C External Override The dry contacts from a BMS system or external device may be assigned to the circuit to de energize the circuit to save power when it is not needed All temperatu...

Страница 61: ...onnected to the circuit for this control mode to function or an RTD failure alarm will be announced Temperature Alarm Filter This minimizes nuisance alarms by forcing the ACS UIT2 to verify that the a...

Страница 62: ...window allows you to set the alarm and trip levels WARNING Shock Hazard National electrical codes require 5 mA Class A ground fault protection devices to be installed when electric floor heating is us...

Страница 63: ...LE TEST The Setup Maint window allows you to enable the Power Cycle test start time and frequency After the start time and frequency are entered the time of the next test will be displayed on this scr...

Страница 64: ...Ambient Control window The Temp Control window allows you to select the temperature control mode to Ambient Control Line Control or PASC This option depends on where the controlling RTD inputs are sit...

Страница 65: ...he events When the sensor for control is returned to service the ACS 30 controller signals the alarm has been cleared returns the circuit to its normal control mode and records both of these events Ra...

Страница 66: ...over the selected period of time before alarming Range 0 999 minutes Default 15 minutes Note Setting the Alarm Filter to 0 minutes is mainly for testing and demonstration purposes Choosing this optio...

Страница 67: ...rip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip WHEN THE GROUND FAULT CURRENT EXCEEDS THIS LEVEL THE...

Страница 68: ...next test will be displayed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 30 Setup Maint window Pipe F...

Страница 69: ...ambient or directly on the pipe itself line Tap Line Fig 3 32 Setup Pipe Freeze Line Control window Setpoint Temperature The setpoint temperature is the desired maintain temperature for the water pipe...

Страница 70: ...its normal control mode and records both of these events Range Power On or Power Off Default Power On External Override The dry contacts from a BMS system or external device may be assigned to the ci...

Страница 71: ...ore alarming Range 0 999 minutes Default 15 minutes Note Setting the Alarm Filter to 0 minutes is mainly for testing and demonstration purposes Choosing this option for normal use may cause nuisance a...

Страница 72: ...UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault current exceeds this level the ACS PCM2 5 turns off the circuit relay Range 10 200 mA Default 30 mA Assigning...

Страница 73: ...will be disabled until the circuit is enabled Fig 3 37 Setup Maint Pipe Freeze Line Control Input the start time and frequency for the Power Cycle test Power Cycle Start Time THE TIME OF DAY TO START...

Страница 74: ...heater should be on or off to maintain a near constant pipe temperature Maintain Temperature Setpoint Fixed design setpoint 40 F 4 C Minimum Ambient ENTER THE MINIMUM AMBIENT TEMPERATURE FOR YOUR INST...

Страница 75: ...he fail safe state Records the events When the sensor for control is returned to service the ACS 30 controller signals the alarm has been cleared returns the circuit to its normal control mode and rec...

Страница 76: ...exists over the selected period of time before alarming Range 0 999 minutes Default 15 minutes Note Setting the Alarm Filter to 0 minutes is mainly for testing and demonstration purposes Choosing thi...

Страница 77: ...und Fault Trip Ground Fault Alarm WHEN THE GROUND FAULT CURRENT EXCEEDS THIS LEVEL THE ACS UIT2 GOES IN ALARM Range 10 200 mA Default 20 mA Ground Fault Trip WHEN THE GROUND FAULT CURRENT EXCEEDS THIS...

Страница 78: ...ext test will be displayed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 44 Setup Maint window Pipe Fr...

Страница 79: ...ng RTD inputs are situated and utilized either measuring the temperature of the environment surrounding the pipe ambient or directly on the pipe itself line Tap Ambient Fig 3 46 Setup Fuel Oil Ambient...

Страница 80: ...Range Power On or Power Off Default Power On External Override The dry contacts from a BMS system or external device may be assigned to the circuit to de energize the circuit to save power when it is...

Страница 81: ...alarm condition continually exists over the selected period of time before alarming Range 0 999 minutes Default 15 minutes Note Setting the Alarm Filter to 0 minutes is mainly for testing and demonstr...

Страница 82: ...ult Alarm and Ground Fault Trip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Alarm When the ground fault cu...

Страница 83: ...Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 51 Setup Maint window Fuel Oil Ambient Control Input the start time and...

Страница 84: ...is below the setpoint temperature the output is turned on Range 1 F 1 C 10 F 6 C Default 5 F 3 C Fail Safe The Fail Safe control button turns the power on or off to the heating cable if the circuit l...

Страница 85: ...rther details Fig 3 54 Setup RTDs window Fuel Oil Line Control Assigning Temperature Alarms Once RTDs have been assigned to the circuit high and low temperature alarms may be set Tap the Alarms button...

Страница 86: ...d on and normal duty cycle control is resumed Range 110 F 43 C 200 F 93 C Default 200 F 93 C High Line Temp Cut Out Enable Disable Enables or disables the high line temp cut out capability When enable...

Страница 87: ...Test The Setup Maint window allows you to enable the Power Cycle test start time and frequency After the start time and frequency are entered the time of the next test will be displayed on this screen...

Страница 88: ...Control window PASC Proportional Ambient Sensing Control PASC takes advantage of the fact that the heat loss from a pipe is proportional to the temperature difference between the pipe and the ambient...

Страница 89: ...g effective power by entering a value less or greater than 100 Range 10 200 Default 100 IMPORTANT If improperly used the Power Adjust parameter can cause the piping to get too cold or too hot If unsur...

Страница 90: ...be assigned to override the system Refer to Appendix Section 5 3 page 130 for further details Fig 3 61 Setup RTDs window Fuel Oil PASC Control Temperature Alarms Once RTDs have been assigned to the c...

Страница 91: ...es an alarm and the relay output is turned off If the high line temperature drops below this threshold minus the deadband the output is turned on and normal duty cycle control is resumed Range 110 F 4...

Страница 92: ...put the Circuit Voltage Voltage 120 208 240 or 277 V Standard ACS PCM2 5 panels Since the C910 485 measures voltage this tab will not appear Default 208 V Assigning Power Cycle Test The Setup Maint wi...

Страница 93: ...F Note Greasy waste mode is also used for XL Trace applications where line control above 40 F is required Fig 3 66 Setup Greasy Waste TM window Temperature Setpoint The pipe temperature setpoint is th...

Страница 94: ...Changes the control status display to indicate that control of the circuit is in the fail safe state Records the events When the sensor for control is returned to service the ACS 30 controller signal...

Страница 95: ...cted period of time before alarming Range 0 999 minutes Default 15 minutes Note Setting the Alarm Filter to 0 minutes is mainly for testing and demonstration purposes Choosing this option for normal u...

Страница 96: ...Alarm and Ground Fault Trip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault curren...

Страница 97: ...f the next test will be displayed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 71 Setup Maint window...

Страница 98: ...s on a snow controller Refer to Appendix 5 3 Connecting External Control Devices on page 130 for connection details Tap External Device Fig 3 73 Setup Roof and Gutter External Device Control window Co...

Страница 99: ...ameters are set tap Setup RTDs window to assign RTDs to the circuit When in external device control mode you have the option of setting up to four inputs through any RTD inputs in your system You must...

Страница 100: ...and Ground Fault Trip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault current exce...

Страница 101: ...next test will be displayed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 77 Setup Maint Window Roof...

Страница 102: ...emperature setpoint for ambient control Range 30 F 1 C 50 F 10 C Default 35 F 2 C Deadband If the measured temperature is above the ambient or high temperature override setpoint temperature plus deadb...

Страница 103: ...to indicate that control of the circuit is in the fail safe state Records the events When the sensor for control is returned to service the ACS 30 controller signals the alarm has been cleared return...

Страница 104: ...and Ground Fault Trip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault current exce...

Страница 105: ...is screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 83 Setup Maint Window Roof Gutter Ambient Temp Control Power...

Страница 106: ...2 C Deadband If the measured temperature is above the ambient or high temperature override setpoint temperature plus deadband the relay output is turned off If the control temperature is below the se...

Страница 107: ...the ACS 30 controller signals the alarm has been cleared returns the circuit to its normal control mode and records both of these events Range Power On or Power Off Default Power On ASSIGNING RTDS Af...

Страница 108: ...and Ground Fault Trip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault current exce...

Страница 109: ...ed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 89 Setup Maint Window Roof Gutter Bracketed Ambient T...

Страница 110: ...efault 55 F 13 C Override Manual This feature provides an additional override capability for the circuit Range 0 10 hours Default 0 hours Hrs On or off Power Off Delay Continue to power the circuit wh...

Страница 111: ...on on the RTD window refer to section 2 2 3 Assigning and Sharing RTD Control and Monitoring on page 30 ASSIGNING GROUND FAULT ALARM AND TRIP LEVEL The G F window allows you to set the alarm and trip...

Страница 112: ...s Since the C910 485 measures voltage this tab will not appear Default 208 V Assigning Power Cycle Test The Setup Maint window allows you to enable the Power Cycle test start time and frequency Once t...

Страница 113: ...NG MODE The Snow Melting control mode prompts you to enter the control parameters for a Surface Snow Melting application In this mode you will be given three different control method options External...

Страница 114: ...erride capability for the circuit Range 0 10 hours Default 0 hours Hrs On or off Power Off Delay Continue to power the circuit when the external control devices contacts open Range 0 10 hours Default...

Страница 115: ...and Ground Fault Trip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault current exce...

Страница 116: ...xt test will be displayed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 101 Setup Voltage Window Snow...

Страница 117: ...erature Tap Ambient Temp Fig 3 103 Setup Snow Melting Ambient Temp Control Window Setpoint Enter the temperature setpoint for ambient control Range 30 F 1 C 50 F 10 C Default 35 F 2 C Deadband If the...

Страница 118: ...or Changes control of the circuit to the fail safe control selected Changes the control status display to indicate that control of the circuit is in the fail safe state Records the events When the sen...

Страница 119: ...and Ground Fault Trip Ground Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes in alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault current exce...

Страница 120: ...next test will be displayed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 107 Setup Maint Window Snow...

Страница 121: ...ow Setpoint Enter the setpoint temperature for surface temperature control Range 30 F 1 C 50 F 10 C Default 40 F 4 C Deadband If the measured temperature is above the setpoint temperature plus deadban...

Страница 122: ...ircuit to the fail safe control selected Changes the control status display to indicate that control of the circuit is in the fail safe state Records the events When the sensor for control is returned...

Страница 123: ...ound Fault Alarm When the ground fault current exceeds this level the ACS UIT2 goes into alarm Range 10 200 mA Default 20 mA Ground Fault Trip When the ground fault current exceeds this level the ACS...

Страница 124: ...t test will be displayed on this screen Note If the circuit is disabled forced on or forced off the power cycle test will be disabled until the circuit is enabled Fig 3 113 Setup Maint Window Snow Mel...

Страница 125: ...1 ASSIGNING A TEMP MONITOR CIRCUIT 4 1 1 SELECTING THE TEMPERATURE MONITORING CIRCUIT The Monitor Only circuits are labeled TM A through TM E and can be accessed from the main screen or from the set...

Страница 126: ...ging style keypad Fig 4 3 Temperature Monitor Circuit Identification keypad ASSIGNING RTDS Once the Temperature Monitoring circuit has been selected and identified tap Setup RTD tab to assign RTDs fro...

Страница 127: ...ow Temp 400 F 204 C Default 200 F 88 C Low Temp Alarm If any RTD assigned to the temperature monitor circuit measures a temperature below this threshold the ACS UIT2 generates an alarm Range 99 F 40 C...

Страница 128: ...ithm that uses the measured ambient temperature desired maintain temperature minimum ambient temperature assumption used during design and size of the smallest pipe diameter to calculate how long the...

Страница 129: ...nts a half hour in time On the Y Axis each mode is labeled Each mode is represented by both the height of the bar and the color of the bar The mode colors are described below Scheduler Dropdown Boxes...

Страница 130: ...30 minute intervals per a 7 day week where each day can be unique Circuits can be set to one of four modes at any given 30 minute interval Off The circuit is completely turned off Economy The circuit...

Страница 131: ...Place a check mark next to each day that you the schedule to be copied to Press OK to finish PRESETS When using the scheduler for an HWAT circuit the presets option will appear on the main window Tap...

Страница 132: ...xternal device input terminals of the C910 485 controller to provide auxiliary override to the temperature input The Roof Gutter De icing and Surface Snow Melting control modes include an External Dev...

Страница 133: ...nalDeviceorSnow Controller DryContact Ground Jumper No 4 3 2 1 ACS PCM2 5 Chassis Ground ACS 30 C910 485 ACS CRM Board RTD Input 6 4 3 C910 485 Controller 12VDC EXTERNALDRYCONTACT COMMON 7 CLOSETOACTI...

Страница 134: ...TIME HRS SUPPLY EMC TEMP LIMIT HEAT SNOW GFEP ST AR T STOP HEA TER CYCLE HIGH TEMPERATURE LIMIT 40 90 50 60 70 80 Red Black White To snow sensors 470 K Resistor 5 1 4 W 15 14 11 10 3 2 1 4 3 2 1 RTDIn...

Страница 135: ...This resistor simulates the RTD input required for the APS 3C which is now supplied by the ACS 30 2 Connect 2 wire grounded shielded cable from terminals 20 and 21 normally open position to the RTD in...

Страница 136: ...external relay such as the Panasonic Model AHN110X1 or equivalent to the yellow active power leads from the GIT 3A 2 Connect 2 wire grounded shielded cable from normally open output terminals of the e...

Страница 137: ...temperature detectors RTD Number The number of the RTD determined by the physical point of connection to a networked device Set Pt Setpoint the desired maintain temperature Status Relay heater on off...

Страница 138: ...any Windows PC The program allows for easy remote configuration of an ACS UIT2 without the limitations of the UIT s display size and its limited modes of data entry Fig 5 13 ACS 30 Program Integrator...

Страница 139: ...nVent com 139 Raychem AR H58692 ACS30UIT2Programming EN 1805 Fig 5 14 ACS 30 Program Integrator Printout...

Страница 140: ...Setup Circuit Current Status Circuit Status Min Max Date System Clock Deadband or DB Setup Frost Heave Setup Floor Heating Setup Pipe Freeze Setup Fuel Oil Setup Greasy Waste Setup Roof and Gutter Set...

Страница 141: ...anual Override Setup Roof and Gutter Min Ambient Temp Setup Pipe Freeze Min Pipe Size Setup Pipe Freeze Setup Fuel Oil Modbus Address System Comm Mode Main Setup Circuit Status Circuit Status RTDs Mod...

Страница 142: ...ing Setpoint Mode Setup HWAT Setup Floor Heating Setup Greasy Waste Slab Temp Setpoint Setup Frost Heave Snow Melting Mode Mode Select Stagger Start System Misc Start Test Setup Circuit State Network...

Страница 143: ...etup Grease TM Waste Setup HWAT Setup Maint Setup Mode Select Setup Pipe Freeze Setup Roof and Gutter Setup RTDs Setup Snow Melting Setup Voltage Status Circuit Status Energy Status Maint Status Min M...

Страница 144: ...nVent com 144 Raychem AR H58692 ACS30UIT2Programming EN 1805...

Страница 145: ...H58692 ACS30UIT2Programming EN 1805 145 Our powerful portfolio of brands CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACER nVent com North America Tel 1 800 545 6258 Fax 1 800 527 5703 thermal info nvent co...