G3 Series EtherNet/IP
TM
Technical Manual
Page 13-135
TDG3EPTM1-9EN
05/18
Subject to change without notice
www.asco.com/g3
13.2
Manifold and I/O Data Sizing Worksheet
Step
1
: Choose appropriate value and place the corresponding Input and Output values in the boxes labeled, “Valve Byte
Requirements” at the bottom of the page
2
: Choose up to sixteen modules to be included on the discrete I/O side of the manifold and place sum of the
corresponding input bytes and output bytes in the boxes labeled, “Sub-Bus Byte Requirements” at the bottom of
the page.
3
: Total the input bytes and output bytes values from the boxes labeled “Sub-Bus Byte Requirements” and “Valve
Byte Requirements” in the boxes labeled “Total Input and Output Bytes for Manifold. This is the total input and
output byte values required for the configured manifold.
Valve Side
Step
Valve Side
Input Bytes
Output Bytes
Status
Enabled
Status
Disabled
1
Up to 32 Solenoid Coils
4
0
4
Digital Modules
Step
Module No.
Description
Input Bytes
Output Bytes
Status
Enabled
Status
Disabled
2
240-203/204
16 Inputs - Terminal Strip
3
2
0
240-205/209
16 Inputs - 8 x 12mm
3
2
0
240-206/210
8 Inputs - 8 x 12mm
2
1
0
240-207
16 Outputs - 8 x 12mm
2
0
2
240-208
8 Outputs - 8 x 12mm
1
0
1
240-211
8 Inputs / 8 Outputs - 8 x 12mm
3
1
1
240-241
Sub – Bus Valve Output
4
0
4
240-300
High Current 8 Outputs – 8 x 12mm
1
0
1
Analog Modules
Step
Module No.
Description
Input Bytes
Output Bytes
Status
Enabled
Status
Disabled
2
240-212/214
4 Inputs
10
8
0
240-213/215/307
2 Inputs/ 2 Outputs
6
4
4
Total Input/Output Size Calculation
Step
Module Position
Model Number
Input Bytes
Output Bytes
2
1
st
2
nd
3
rd
4
th
5
th
6
th
7
th
8
th
9
th
10
th
11
th
12
th
13
th
14
th
15
th
16
th
Sub-Bus Byte Requirements:
Optional Diagnostic Word:
2
0
1
Valve Byte Requirements:
3
Total Input and Output Bytes for Manifold
Содержание G3 Series EtherNet/IP