RTD Module / Alarm Settings
Allows the Low and High alarms of each RTD Input channel to be set. This parameter generates a visual and logical (bit) when
set value is achieved.
A) Press the SET button to enter the
Alarm Settings sub-menu.
B) Press the NEXT button to scroll through
the RTD Input channels.
C) Press the SET button to enter the alarm
setting for the selected Input channel.
D)
Press the NEXT button to select the Lo
or High setting for the selected
channel.
E) Press the SET button to select the
change process for the chosen alarm.
The first digit/sign will be highlighted.
F) Press the NEXT button to choose the
value, or the SET button to select and
move to the next digit.
G) Press the NEXT button to choose “Y” or
“N” Select. Then press the SET Button
to Accept.
NOTE!
SET ALARM
CHANNEL CH0
SET ALRM CH1
LO = -200.0 C
SET ALRM CH1
LO =
-
200.0 C
ACCEPT
50.0 C
Y
N
ALARM
SETTINGS
•
When alarm values are set to maximum/minimum values, the alarm function is
disabled.
•
Factory default settings for all alarms are disabled.