4.7
Diagnostics
Communication Module LED Functions
Upon power up, the LEDs indicate the status of the unit. There are three LEDs on the G3 EtherNet node.
These LEDs are described below.
LED Name
Color
Status
Description
MODULE
STATUS
Off
OFF
No power applied to
+24V
NODE/ IN
.
Green
ON
Device operational. The module is operating correctly.
FLASHING
Standby. The module has not been configured.
Red
ON
Major fault. A major internal error has been detected.
FLASHING
Minor fault. A minor recoverable fault has been detected.
Self -Test Mode - An error has occurred in the initialization process.
Green
Red
FLASHING
Self -Test Mode.
NETWORK STATUS
Off
OFF
IP address has not been assigned to node or no power applied to
+24V
NODE/ IN
.
Green
ON
Connected. The module has established an EtherNet/IP
TM
connection.
FLASHING
No connection. There are no EtherNet/IP
TM
connections established to the
module.
Red
ON
Duplicate IP address. The module has detected that its IP address is
already being used elsewhere on the network
FLASHING
EtherNet/IP
TM
connection has timed out. One or more of the connections
for which this module is the target has timed out.
ACTIVITY/LINK
Green
OFF
No EtherNet connection is detected
ON
The module is connected to an EtherNet
TM
network
FLASHING
The LED flashes each time a packet is received or transmitted.