OPERATOR & MAINTENANCE MANUAL

 

 

PAGE

34

 

When

 

building

 

the

 

foundation,

 

specific

 

attention

 

needs

 

to

 

be

 

paid

 

to

 

the

 

following:

 

 

 

The

 

generator

 

base

 

must

 

be

 

isolated

 

from

 

the

 

building

 

foundation.

 

 

Depth

 

and

 

width

 

to

 

meet

 

the

 

basic

 

requirements.

   

 

Foundation

 

must

 

be

 

strong

 

enough

 

to

 

take

 

the

 

impact

 

and

 

running

 

force

 

of

 

the

 

machine.

 

 

Ensure

 

that

 

no

 

vibration

 

is

 

transmitted

 

to

 

the

 

building

 

foundation

 

when

 

the

 

unit

 

starts.

 

 

Ease

 

of

 

maintenance

 

and

 

servicability

 

operations.

 

 

When

 

calculating

 

the

 

length

 

L

 

and

 

width

 

B

 

of

 

the

 

base

 

allow

 

an

 

additional

 

100

300mm

 

on

 

each

 

side.

 

 

The

 

base

 

should

 

be

 

higher

 

than

 

engine

 

room

 

floor

 

by

 

20

300mm.

   

 

 

 

Mounting

 

the

 

Generator

 

The

 

generator

 

is

 

mounted

 

on

 

a

 

steel

base

 

tank

 

that

 

provides

 

adequate

 

support.

 

Vibration

 

isolators

 

are

 

recommended

 

between

 

the

 

base

 

tank

 

and

 

the

 

foundation

 

to

 

provide

 

stable

 

operation

 

and

 

avoid

 

installation

 

damage.

 

Bolting

 

the

 

generator

 

directly

 

to

 

the

 

floor

 

or

 

foundation

 

can

 

result

 

in

 

excessive

 

noise

 

and

 

vibration,

 

and

 

possible

 

damage

 

to

 

the

 

generator

 

and

 

floor

 

foundation.

 

Mount

 

the

 

generator

 

on

 

a

 

substantial

 

and

 

level

 

base

 

such

 

as

 

a

 

concrete

 

pad.

 

Use

 

20mm

 

anchored

 

mounting

 

bolts

 

to

 

secure

 

the

 

vibration

 

isolators

 

to

 

the

 

base

 

tank

 

using

 

flat

 

or

 

bevel

 

washers

 

and

 

a

 

hexagonal

 

nut

 

for

 

each

 

bolt.

 

The

 

isolators

 

should

 

be

 

located

 

as

 

shown

 

on

 

the

 

generator

 

outline

 

drawing.

   

 

 

 

Incorrect

 

installation

 

or

 

service

 

can

 

result

 

in

 

severe

 

personal

 

injury

 

or

 

death,

 

and/or

 

equipment

 

damage.

 

Only

 

qualified

 

service

 

personnel

 

should

 

be

 

allowed

 

to

 

perform

 

electrical

 

and

 

mechanical

 

component

 

installation.

 

 

Never

 

install

 

the

 

genset

 

near

 

combustible

 

materials.

 

Locate

 

the

 

genset

 

such

 

that

 

combustible

 

material

 

can

 

not

 

accumulate

 

under

 

the

 

machine.

 

The

 

possibility

 

exists

 

of

 

fire

 

or

 

explosion,

 

causing

 

damage

 

to

 

the

 

equipment

 

and

 

or

 

severe

 

bodily

 

harm

 

or

 

even

 

death!

 

Содержание S10KS

Страница 1: ...PROMAC LEADING THE WAY OPERATOR MAINTENANCE MANUAL...

Страница 2: ...S10KS GENERATING SET OPERATOR MAINTENANCE MANUAL Edition A A Date 5 May 2011...

Страница 3: ...tor Specifications 11 3 3 Generator Layout and Main Components 12 3 4 Control Cabinet and Panel 14 3 4 1 Control Cabinet 14 3 4 2 Control Panel 16 3 4 3 AMF25 Controller 21 3 5 Generator Wiring Diagra...

Страница 4: ...Automatic Operation Mode 51 5 8 Shutting Down Genset 51 5 9 Lifting and Transportation 52 5 10 Overnight Storage 52 5 11 Long term Storage 52 6 Maintenance 52 6 1 Periodic Maintenance Schedule 53 6 2...

Страница 5: ...anuals if necessary This manual is not to be reproduced in any form or by any means without the express written approval of Promac Sales Pty Ltd ENGINE EXHAUST can cause serious injury or even death U...

Страница 6: ...mbol the industry s Safety Alert Symbol is used throughout this manual and on labels attached to the machine itself It warns of the potential for personal injury It is essential that you carefully rea...

Страница 7: ...ive Equipment PPE is worn while working on generators Stay clear of any moving parts 2 2 Safety During Transportation Always shut the engine down before transporting Never transport the generator with...

Страница 8: ...any of the generator s electrical terminals unprotected Ensure all connection points and their accessories have been correctly earthed Verify and ensure that all electrical power connections and auxil...

Страница 9: ...ine when the air cleaner is removed Engine backfire can cause serious burns Do not remove the radiator cap while the engine is running Allow the coolant to sufficiently cool before removing the radiat...

Страница 10: ...s are used on the product and throughout this manual TABLE 1 SAFETY LABELS LABEL DESCRIPTION 1 Read the Operator Manual 2 No sparks or naked flames near the machine 3 Press the emergency stop switch w...

Страница 11: ...s and caps are secure for transporting or relocating Warning Read this label before lifting and transporting Only use designated lifting points on generator Warning 1 Disconnect the battery before ser...

Страница 12: ...ne Warning High voltage Note 1 Check the coolant level in the radiator 2 Check the coolant level in the overflow bottle 3 Check the engine oil level Warning Not a lifting point Note Lubrication oil in...

Страница 13: ...ERATOR MAINTENANCE MANUAL PAGE 9 Note Forklifting point Note Bottom drain bund Diesel fuelling point Coolant refill point and type of coolant Main Isolator Switch Off On Switch Circuit Breaker Type Si...

Страница 14: ...displaying all warning alarms and performing automatic shutdowns on fault signals 50 C designed cooling system The engine and alternator have rubber av mounts installed to reduce vibration High anti...

Страница 15: ...CATIONS Model Kubota D1105 BG Number of Cylinders 3 Bore mm 78 Stroke mm 78 4 Engine Speed rpm 1500 Prime Power kW 8 0 Standby Power kW 8 8 Compression Ratio 24 1 Displacement L 1 123 Cooling System W...

Страница 16: ...OPERATOR MAINTENANCE MANUAL PAGE 12 3 3 Generator Layout and Major Components...

Страница 17: ...x 1060 x 1070mm 2 Fire extinguisher bracket Designed for 9kg ABE fire extinguisher 3 Field wiring cabinet 4 Base Size 2390 x 1080 x 400mm 5 Control cabinet assembly 6 Spark Arrestor Rating 8m3 min 7...

Страница 18: ...OPERATOR MAINTENANCE MANUAL PAGE 14 3 4 Control Cabinet and Panel 3 4 1 Control Cabinet...

Страница 19: ...ode the controller will be in Automatic Mains Failure function With the switch in ISLAND mode the generator can be remotely started by closing the remote start terminals Both AMF and Remote Start requ...

Страница 20: ...OPERATOR MAINTENANCE MANUAL PAGE 16 3 4 2 Control Panel...

Страница 21: ...y Charger Selector Switch 8 Audible Alarm 9 Master Control Switch 10 Controller Intelilite AMF 25 11 Earth Leakage Relay ELR Schneider Vigirex RH99P Panel mounted 12 RCD Test Point Push Button Mains c...

Страница 22: ...Lamp is not illuminated the ELR relay is bypassed 4 RCD Status Lamp Globe Test Button The RCD Status Lamp Globe Test Button 4 is used to test the function of the globe of the RCD status lamp 3 5 Main...

Страница 23: ...2 allows power to the RCD Test Point 13 13 RCD Test Point The RCD Test Point 13 is used to test the earth leakage protection function When an earth leakage greater than the adjustable ELR s setpoint o...

Страница 24: ...t power from the load side of the RCD MCB to the 20A single phase GPO in the field wiring cabinet RCD capability exists to protect the end user Note If a fault occurs test accordingly before reinstati...

Страница 25: ...ng or holding the button for more than 2s will cancel the current phase of stop sequence ramping the power down or cooling and the next phase will continue 3 FAULT RESET button Use this button to ackn...

Страница 26: ...the Red LED will start flashing After pressing the Fault Reset button the LED will turn off if no alarm is active or will become constant if the alarm is still active 10 Gen Set Voltage OK If the gen...

Страница 27: ...in the history page Display Screens and Pages Structure The displayed information is structured into pages and screens Use the PAGE button to scroll through the pages 1 The Measurement pages consist o...

Страница 28: ...OPERATOR MAINTENANCE MANUAL PAGE 24 Alarms...

Страница 29: ...OPERATOR MAINTENANCE MANUAL PAGE 25 Browsing ECU Alarms...

Страница 30: ...OPERATOR MAINTENANCE MANUAL PAGE 26...

Страница 31: ...OPERATOR MAINTENANCE MANUAL PAGE 27...

Страница 32: ...OPERATOR MAINTENANCE MANUAL PAGE 28 3 4 5 Field Wiring Cabinet...

Страница 33: ...If the load side has another MEN Link connected the generator side MEN Link must be disconnected A spare terminal 4 is provided The earth leakage relay must also be bypassed in the control cabinet Thi...

Страница 34: ...binet The two switches are wired in series When activated the emergency stop activated by pushing the red button will turn off the fuel solenoid resulting in the engine shutting down Rotate button to...

Страница 35: ...OPERATOR MAINTENANCE MANUAL PAGE 31 3 5 Generator Wiring Diagram...

Страница 36: ...ustic Material consideration Consider the following when selecting acoustic material Foam is not recommended as an acoustic material because of it s low density it is a poor acoustic insulator And not...

Страница 37: ...equires greater noise and vibration attenuation the generator should be installed in a manner that reduces the impact of vibration on buildings The base height is calculated as follows The depth H of...

Страница 38: ...on to provide stable operation and avoid installation damage Bolting the generator directly to the floor or foundation can result in excessive noise and vibration and possible damage to the generator...

Страница 39: ...deterioration of the insulation and will result in short circuits Foreign materials such as dust sand lint and abrasive materials have a tendency to cause excessive wear to engine and alternator part...

Страница 40: ...OPERATOR MAINTENANCE MANUAL PAGE 36...

Страница 41: ...indoors it must be protected from the environment while having good ventilation and cooling Some considerations for planning a room or enclosure are Never use the generator room for storage The room...

Страница 42: ...r to protect the engine when the ambient temperature is around 50 C or close to 15 C the equipment load must be reduced or engine life may be compromised 4 7 MECHANICAL CONNECTIONS After considering a...

Страница 43: ...ience of having a fuel supply tank mounted at the generator These tanks are designed to be contained in a rectangular base on which the engine generator set is mounted Generally these tanks only incre...

Страница 44: ...ery 400 hours Air trapped in the filter is purged by the vent plug Fuel water separator is a device designed to separate gross amounts of fuel and suspended solids from the wastewater effluents of fue...

Страница 45: ...il must have a high viscosity index Multi grade oils having relatively low viscosity For example SAE 10W 30 can provide superior lubrication at both low and high temperatures Such oils are available c...

Страница 46: ...unwanted water This process must be completed whilst the engine is shut down as it may cause injury 4 7 4 Ventilation and Cooling system As the generator produces a high volume of heat ventilation and...

Страница 47: ...the cable DANGER If the load exceeds the allowable amperage overheating may cause damage to cables If the cables are too long there will be excessive voltage drop It may result in fire personal injur...

Страница 48: ...ery cables before running the machine Connect the red cable to the positive terminal post Connect the black cable to the negative terminal post WARNING If the terminal is not connected it may result i...

Страница 49: ...the incoming AC mains supply If the mains supply is satisfactory the load is run through the ATS and the generator will not run On the contrary the generator will run if the mains power is abnormal T...

Страница 50: ...ith local regulations and standards Make sure the fan belt and hoses on the engine have no loose connections or are fraying Tighten or replace as required Check the battery cables are firmly secured t...

Страница 51: ...e level is below the lower limit Select the appropriate engine oil Open the access door remove oil cap Add engine oil to bring oil level NO higher than FULL mark on the dipstick Tighten the oil inlet...

Страница 52: ...e radiator cap Fill coolant up to the radiator inlet top Reinstall and tighten the coolant inlet and radiator caps WARNING Avoid injury The coolant will be hot and can burn skin Built up pressure may...

Страница 53: ...5 the fuel solenoid is energised and after a one second delay the starter motor will crank the engine for the duration of the crank timer preset on PLC three attempts 7 After the engine successfully s...

Страница 54: ...on the LCD or audible alarm Check for any leakage of coolant oil or fuel Check for any unusual vibration or noise Check for any unusual colour from the exhaust Under normal conditions the exhaust gas...

Страница 55: ...or 5 7 Stopping Generator Under Automatic Operation Mode If the mains supply returns and the generator does not stop running follow the steps listed below Turn every switch and circuit breaker on the...

Страница 56: ...ng the generator overnight make sure all access doors are closed and padlocked CAUTION Do not store generator in a low lying area as large quantities of water can enter the generators electrical mecha...

Страница 57: ...ine oil fuel and coolant level Check for leaks oil fuel and coolant Check air cleaner dust cap Check generator visually Check battery charging system Check drive belt tension Drain water sediment from...

Страница 58: ...om inside Use a clean cloth to wipe the filter sealing surface and the inside of the outlet tube Reinstall the air cleaner in the reverse order 6 3 2 Change Air Filter Element Loosen clips in the air...

Страница 59: ...Pour new coolant into the radiator up to the radiator inlet top Close the radiator cap and coolant inlet cap WARNING Avoid injury The radiator will be hot and can burn skin Built up pressure may cause...

Страница 60: ...ighten the oil inlet cap and close the access door 6 5 2 Change Oil Filter Drain engine oil completely as described in 6 5 1 Loosen and remove the oil filter Add engine oil into a new oil filter Lubri...

Страница 61: ...drain fuel and water Loosen and remove fuel filter Add fuel into a new fuel filter Lubricate the new gasket will oil Screw the new filter into place and tighten accordingly DANGER Do not smoke while y...

Страница 62: ...ve 6 Repair or change the thermostat Low fuel level 1 Fuel is insufficient 1 Add fuel 2 Fuel hose has a leak 2 Tighten or change fuel hose 3 Fuel tank has a leak 3 Repair or change fuel tank 4 Fuel fi...

Страница 63: ...nge gauze filter 5 Air is mixed in fuel line 5 Bleed the air Engine starts but stalls at once 1 Fuel hose has a leak 1 Tighten or change fuel hose 2 Fuel filter is clogged 2 Drain water sediment or Ch...

Страница 64: ...EADING THE WAY Promac Sales Email sales promac net au Phone 61 8 6254 1800 Fax 61 8 6254 1899 Office 11 Poole Street Welshpool Western Australia 6106 Postal Address PO Box 538 Welshpool Western Austra...

Отзывы: