OPERATOR & MAINTENANCE MANUAL
PAGE
‐
20
17.
Main
Isolator
(50A
2P)
The
lockable
two
‐
pole
Main
Isolator
(50A)
(17)
is
located
on
the
control
panel.
When
the
electric
current
exceeds
50A,
it
will
automatically
trip
to
the
“fault”
position
and
interrupt
all
power
from
the
load
side
of
the
circuit
breaker.
Note:
The
generator
will
still
supply
power
to
the
line
side
of
breaker.
18.
Single
Phase
RCD/MCB
Combo
Protecting
20A
Single
Phase
Outlet
The
20A
Single
Phase
RCD/MCB
Combo
device
(18)
is
located
on
the
control
panel.
When
the
electric
current
is
greater
than
20A
or
a
residual
current
of
greater
value
than
30ma
is
detected,
this
device
will
automatically
trip
to
the
“Fault”
position.
This
will
interrupt
power
from
the
load
side
of
the
RCD/MCB
to
the
20A
single
phase
GPO
in
the
field
wiring
cabinet.
RCD
capability
exists
to
protect
the
end
user.
Note:
If
a
fault
occurs,
test
accordingly
before
reinstating
RCD/MCB
19
&
20.
Single
Phase
RCD/MCB
Combo
Protecting
15A
Single
Phase
Outlets
The
16A
Single
‐
phase
RCD/MCB
Combo
devices
(19)
and
(20)
are
located
on
the
control
panel.
When
the
electric
current
is
greater
than
16A
or
a
residual
current
of
greater
value
than
30ma
is
detected,
this
device
will
automatically
trip
to
the
“Fault”
position.
This
will
interrupt
power
from
the
load
side
of
the
RCD/MCB
to
the
respective
GPO
in
the
field
wiring
cabinet.
RCD
capability
exists
to
protect
the
end
user.
Note:
If
a
fault
occurs,
test
accordingly
before
reinstating
RCD/MCB.
.
WARNING:
Before
shutting
down
the
generator
or
performing
any
service,
make
sure
the
Main
Isolator
is
in
the
“OFF”
position
and
locked.
Содержание S10KS
Страница 1: ...PROMAC LEADING THE WAY OPERATOR MAINTENANCE MANUAL...
Страница 2: ...S10KS GENERATING SET OPERATOR MAINTENANCE MANUAL Edition A A Date 5 May 2011...
Страница 16: ...OPERATOR MAINTENANCE MANUAL PAGE 12 3 3 Generator Layout and Major Components...
Страница 18: ...OPERATOR MAINTENANCE MANUAL PAGE 14 3 4 Control Cabinet and Panel 3 4 1 Control Cabinet...
Страница 20: ...OPERATOR MAINTENANCE MANUAL PAGE 16 3 4 2 Control Panel...
Страница 28: ...OPERATOR MAINTENANCE MANUAL PAGE 24 Alarms...
Страница 29: ...OPERATOR MAINTENANCE MANUAL PAGE 25 Browsing ECU Alarms...
Страница 30: ...OPERATOR MAINTENANCE MANUAL PAGE 26...
Страница 31: ...OPERATOR MAINTENANCE MANUAL PAGE 27...
Страница 32: ...OPERATOR MAINTENANCE MANUAL PAGE 28 3 4 5 Field Wiring Cabinet...
Страница 35: ...OPERATOR MAINTENANCE MANUAL PAGE 31 3 5 Generator Wiring Diagram...
Страница 40: ...OPERATOR MAINTENANCE MANUAL PAGE 36...