OPERATOR & MAINTENANCE MANUAL
PAGE
‐
21
3.4.3
AMF
25
Controller
TABLE
5:
PUSH
BUTTONS
REF
NAME
DESCRIPTION
1
START
button. Works in MAN mode only. Press this button
to initiate the start sequence of the engine.
2
STOP
button. Works in MAN mode only. Press this button
to initiate the stop sequence of the gen-set. Repeated
pressing or holding the button for more than 2s will cancel
the current phase of stop sequence (ramping the power
down or cooling) and the next phase will continue.
3
FAULT RESET
button. Use this button to acknowledge
alarms and deactivate the horn output. Inactive alarms will
disappear immediately and status of active alarms will be
changed to "confirmed" this will allow the alarm to reset
when the fault condition is alleviated.
4
HORN RESET
button. Use this button to deactivate the
horn output without acknowledging the alarms.
Содержание S10KS
Страница 1: ...PROMAC LEADING THE WAY OPERATOR MAINTENANCE MANUAL...
Страница 2: ...S10KS GENERATING SET OPERATOR MAINTENANCE MANUAL Edition A A Date 5 May 2011...
Страница 16: ...OPERATOR MAINTENANCE MANUAL PAGE 12 3 3 Generator Layout and Major Components...
Страница 18: ...OPERATOR MAINTENANCE MANUAL PAGE 14 3 4 Control Cabinet and Panel 3 4 1 Control Cabinet...
Страница 20: ...OPERATOR MAINTENANCE MANUAL PAGE 16 3 4 2 Control Panel...
Страница 28: ...OPERATOR MAINTENANCE MANUAL PAGE 24 Alarms...
Страница 29: ...OPERATOR MAINTENANCE MANUAL PAGE 25 Browsing ECU Alarms...
Страница 30: ...OPERATOR MAINTENANCE MANUAL PAGE 26...
Страница 31: ...OPERATOR MAINTENANCE MANUAL PAGE 27...
Страница 32: ...OPERATOR MAINTENANCE MANUAL PAGE 28 3 4 5 Field Wiring Cabinet...
Страница 35: ...OPERATOR MAINTENANCE MANUAL PAGE 31 3 5 Generator Wiring Diagram...
Страница 40: ...OPERATOR MAINTENANCE MANUAL PAGE 36...