16
(5) Wiring of external control input
Wiring method to control parts feeder
’
s ON/OFF from
outside when the function is a standard setting, is
explained.
①
Check that between 24V-+V terminals is short-circuited
with jumper. In case jumper or control wire etc. is not in,
short-circuit them
②
The jumper wire between terminals of X1 and 0V is
removed, and the relay contact (or NPN transistor) is
connected between these terminals. Do not remove
jumper 1.
※
When the ON/OFF delay timer is intended to be used, use the IN input. Please prepare cables used for
control by your company.
When function
№
. JO2 is set as 1 (standard).
・
With short-circuited state between X1
-
0V, parts feeder is driven (for NPN transistor output, it is Lo level)
・
With open state between X1
-
0V, parts feeder is stopped (for NPN transistor output, it is High level)
When the logic is reversed (JO2 is set as 0) by the function, it is driven with open state. Please refer to P.39
for the setting of the function JO2.
Please refer to the next page when controlling by the PNP transistor output or using it for the hopper control.
Note 1
The current of DC24V 7mA flows between terminals X1-0V. Please be careful of the noise
enough because it is a minute electric current.
Note 2
The cable length of signal input line (24V, +V, X1, 0V) should be within 10m. Adopt a twist wiring if it is
possible.
In case of no external control used
When the external control terminal is not used, make function J02 setting as "1" and have the
external control input terminal short-circuited (at two positions of 24V-+V and X1-0V). The controller
drives continuously. Even if the setting of J02 is made "0" and the external control input terminal is
opened, it becomes a continuous driving.
Caution
24V, X1 and 0V terminals have polarity. Please be
careful of wiring enough. In addition, please never
connect it to AC power.
Caution
Parts feeder's ON/OFF control must use the
external control input terminal. ON/OFF control by
the power supply is impossible.