13
(3) Connection of load line
Please connect the load line (load cable of the parts
feeder attachment) to the terminal board through
controller's cable ground. As the voltage of max
AC200V applies to this terminal, be careful of the wiring
enough. Please refer to the following note 1 when
extending the line.
Name of terminal
board
Color of wiring
1
Black 1 or Red
2
Black 2 or White
Earth bar
Green/Yellow, Green or Black
*1 Please do not connect this to other than the parts
feeder. It breaks down.
*2 Please refer to P.17 when connecting the hopper
separately placed as wiring of level switch is
necessary.
*3 The connection to the controller terminal board must be
done by using the round type crimping terminal (The
terminal screw: M4).
Note 1
Extension of cable length
Please use the size of 2.0mm
2
or more when you change the cable. Moreover, when extending it to 3m or
more, please connect it to the main body cable by extending it to the vicinity of the main body by using the
cable of the size of 2.5mm
2
or more, and using the relay BOX. Extension length shall be 10m or less.
Note 2 There is a possibility that the noise is added in the load cable. When the load cable is close to equipments
which dislike noise, please take measures such as separation of wiring route from them and the use of
shield cable. Moreover, do not put the load cable and the signal line into the same duct (protection tube).
Note 3 Correct earth shall be checked by protection continuity test machine after
the earth construction work ends.
When the earth is imperfect, it is likely to get an electric shock.
*
Notes for transformer usage
Please note not only the current rating but also the voltage descent due to the inrush current, etc. when you
supply power to the controller through the transformer. Please note enough the voltage descent at power supply
ON and the trouble due to the noise especially when the transformer is set commonly with other equipments.
Please consult the transformer maker about details of the problem when supplying the power to the controller
(inverter). Please refer to the paragraph of the input in P.53 for controller's inrush current. Moreover, to reduce
the influence by the noise, the use of the shielded wire or wiring of a distance as short as possible is
recommended.
負荷ケーブル
アースバー
N
L
1
2
黒1
パーツフィーダ等へ
黒2
緑/黄
端子台(M4)
電源ケーブル
Earth bar
Terminal block
(M4)
Black 1
Black 2
Green/Yellow
To parts feeder and others
Power cable
Load cable