26
•
Single Connections
3.8 Deviation Counter Clear Signal ERC
The deviation counter clear signal (ERC) is active in the following 4
situations:
1. home return is complete;
2. the end-limit switch is active;
3. an alarm signal stops OUT and DIR signals;
4. an emergency stop command is issued by software (operator).
The relative signal name, pin number and axis number are shown in the
following table.
CN2 Pin No
Signal Name
Axis #
8
ERC1
26
ERC2
58
ERC3
76
ERC4
The ERC signal is used to clear the deviation counter of servomotor driver.
The ERC output circuit is in the open collector with maximum 35 V external
power at 50mA driving capability.
For more details of the ERC operation,
please refer to section 4.2.3.
from PCL6045
CN2
Inside PPCI7443
35V 50mA Max.
EXGND
ERC