8
• The quality of outdoor air must also be considered. Be
sure that the combustion air intake is not located near a
source of solvent fumes or other chemicals which can
cause corrosion of the furnace combustion system.
(See page 5 for a sample list of substances).
• Route piping as direct as possible between the furnace
and the outdoors. Longer vent runs require larger
diameters. Vent piping must be sloped upwards 1/4”
per foot in the direction from the furnace to the terminal.
This ensures that any condensate flows back to the
condensate disposal system.
• When a Direct Vent (2-pipe) system is used, the
combustion air intake and the vent exhaust must be
located in the same atmospheric pressure zone. This
means both pipes must exit the building through the
same portion of exterior wall or roof as shown in Figure
20, page 33.
• Piping must be mechanically supported so that its
weight does not bear on the furnace. Pipe supports
must be installed a minimum of every 5 feet along the
vent run to ensure no displacement after installation.
Supports may be at shorter intervals if necessary to
ensure that there are no sagging sections that can trap
condensate. It is recommended to install couplings
along the vent pipe, on either side of the exterior wall
(Figure 20). These couplings may be required by local
code.
• If breakable connections are required in the combustion
air inlet pipe (if present) and exhaust vent piping, then
straight neoprene couplings for 2” or 3” piping with
hose clamps can be used. These couplings can be
ordered through your local furnace distributor. To install
a coupling:
1. Slide the rubber coupling over the end of the pipe
that is attached to the furnace and secure it with
one of the hose clamps.
2. Slide the other end of the rubber coupling onto the
other pipe from the vent.
3. Secure the coupling with the second hose clamp,
ensuring that the connection is tight and leak free.
Outdoor Terminations - Horizontal Venting
• Vent and combustion air intake terminations shall be
installed as shown in Figures 1 & 2 (page 9) and in
accordance with these instructions:
• Vent termination clearances must be consistent with the
NFGC, ANSI 2223.1/NFPA 54 and/or the CSA B149.1,
Natural Gas and Propane Installation Code. Table 12
(page 32) lists the necessary distances from the vent
termination to windows and building air intakes.
• Vent and combustion air intake terminations must
be located to ensure proper furnace operation and
conformance to applicable codes. A vent terminal
must be located at least 3 feet above any forced air
inlet located within 10 feet. This does not apply to the
combustion air inlet of a direct vent (two pipe) appliance.
In Canada, CSA B149.1 takes precedence over these
instructions. See Table 12 (page 32).
total length, including the equivalent fitting lengths, must
be less than the maximum length specified in the table.
Condensing furnace combustion products have very little
buoyancy, so Table 2 is to be used without consideration
of any vertical rise in the piping.
Vent Pipe Material
Vent and combustion air pipe and fittings must be one of
the following materials in the list and must conform to the
indicated ANSI/ASTM standards. Cement must conform
to ASTM Standard D2564 for PVC and Standard D2235
for ABS. PVC primer must meet standard ASTM F656.
When joining PVC piping to ABS, use PVC solvent cement.
(See procedure specified in ASTM Standard D3138).
In Canada, all plastic vent pipes and fittings including
any cement, cleaners, or primers must be certified as a
system to ULC S636. However this requirement does not
apply to piping internal to the furnace.
Materials
Standards
SCHEDULE 40PVC ............................................... D1785
PVC-DWV .............................................................. D2665
SDR-21 & SDR-26 ................................................. D2241
ABS-DWV .............................................................. D2661
SCHEDULE 40 ABS .............................................. F628
FOAM / CELLULAR CORE PVC ........................... F891
Vent Pipe Installation
CAUTION:
Combustion air must not be drawn from a
corrosive atmosphere.
This furnace has been certified for installation with zero
clearance between vent piping and combustible surfaces.
However, it is good practice to allow space for convenience
in installation and service.
• In the absence of local codes, the location of any
combustion air inlet relative to any vent terminal must
be at least 8 inches. This includes installations involving
more than one furnace.
Maximum Direct Vent, Dual Pipe Length (FT.)
CMF95 INPUTS
(BTU)
INLET / OUTLET
2” Diameter
INLET / OUTLET
3” Diameter
45,000
30
60
72,000
30
60
†
NOTES:
1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, subtract
5ft for each additional 2” short radiious elbow, subtract 3.5 ft. for
each additional 3 inch long radius elbow, and 7 ft. for each additional
3 inch short radius elbow.
2. Two 45 degree elbows are equivalent to one 90 degree elbow.
3. This table applies for elevations from sea level to 2,000 ft. For higher
elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.
Table 2. Vent Pipe Lengths