22
Heat Anticipator
Set the heat anticipator according to the instructions
supplied by the thermostat manufacturer.
To determine
the heat anticipator setting:
1. Add the current draw of the system components; or
2. Measure the current flow on the thermostat
R
-
W
circuit
after the circulating blower motor has started.
Figure 16. Line Voltage Field Wiring
Field Supplied
Disconnect w/in
Sight of Furnace
Field Supplied
Panel Connector
Field Supplied
Fused Service
Panel
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Black
White
Black
White
Black
White
Field Line Voltage Wiring
Factory Line Voltage Wiring
Ground
Ground
Junction Box (may be int. or ext. to the furnace). These
connections can be made in the field supplied disconnect
at the furnace. NOTE: Connections made within the furnace
burner compartment do not require a junction box.
Ground
Furnace
Model
Number
CMF95-
Furnace
Input
(Btuh)
Cabinet
Width
(in.)
Nominal
Electrical
Supply
Maximum
Operating
Voltage
Minimum
Operating
Voltage
Maximum
Furnace
Amperes
Minimum
Wire
Gauge
Maximum
Fuse or Circuit
Breaker Amps*
Minimum
Circuit
Ampacity
1
Mamimum
Overcurrent
Protection
2
045
45,000
18
115-60-1
127
103
11.0
14
20
13.1
21.7
072
72,000
18
115-60-1
127
103
10.4
14
20
12.4
20.4
NOTE:
Minimum wire gauge and maximum fuse/circuit breaker amperage are based on MCA
1
and MOP
2
calculations. This furnace is
approved for installation with a 15 or 20 amp fuse/circuit breaker however wiring sizing must adhere to current version of the NEC and/or
applicable local codes depending upon the overcurrent protection.
Thermostat Wire Gauge
Recommended Thermostat Wire Length
2 - wire - Heating
4 or 5 wire - Cooling
24
55 ft.
25 ft.
22
90 ft.
45 ft.
20
140 ft.
70 ft.
18
225 ft.
110 ft.
*
Time-delay fuses or circuit breakers are required.
Table 4. Wire Length & Voltage Specifications
Figure 15. Low Voltage Field, Four-wire
Heating/Cooling Applications
RC
YG
W
STATUS
FLAME
GREEN
RED
180
COOL
HEA
T
120
90
60
YELLOW
BLOWER
OFF
DELAY
LO
W
ML
MH
HIGH
EA
C
L1
XFMR
HUM
COM
SPEED
SELECT
3 AMP
FUSE
24V
5
NEUTRALS
ROOM
THERMOSTAT
A/C CONDENSING UNIT
CONDENSING UNIT
CONTROL BOX
EXPANSION PORT
(MOTOR CONNECTION)
FIELD WIRING
LOW VOLTAGE
CONNECTION
R
C
Y
G
W
NOTE: The “Y” terminal
on the control board
must be connected to the
thermostat for proper
cooling mode operation.
Connect
R & W
For Heating
Only
2
ELECTRONIC AIR CLEANER
MOTOR SPEED TAPS
(NOT USED)
HUMIDIFIER TAP
NEUTRAL LEADS
6 3
4 1
7
8
9
5
2
6 3
4 1
FA
N