background image

27

If the furnace fails to operate check the following:

•  Is the thermostat operating properly?

•  Are the blower compartment door(s) in place?

•  Is the furnace disconnect closed?

•  Has the circuit breaker tripped or the control board fuse 

burned open?

•  Is the gas turned on?

•  Are any manual reset switches open?

•  Is the filter dirty or plugged?

•  Is the flame sensor coated? (Remove and clean with 

steel wool. 

(Do not use emery cloth or sandpaper!)

•  Is there blockage in the condensate drain switch? Also 

verify that there is no double trapping of condensate.

•  Is the secondary heat exchanger free of debris and 

clogs?

•  Is evaporator coil clean and free of debris (If applicable).

•  Are all the LED’s on the furnace control board constantly 

ON? If not, refer to Table 6 or the wiring diagram (Figure 

18, page 29) to determine fault condition.

IMPORTANT NOTE: The furnace will lock out after 5 
failed attempts for ignition and will try again every 
hour if the call for heat remains.

•  If the inducer blower is operating, and items above have 

been verified, check the blower limit switch and reset 

if necessary. See Figure 17 for component location.

•  If the furnace operates when the Blower Limit Switch is 

reset, contact a qualified service technician to identify 

and repair the problem.

•  If  the  furnace  still  doesn’t  operate,  check  the  flame 

roll-out switch (Figure 17) and reset if necessary.

•  If the furnace operates when the flame rollout switch is 

reset, contact a qualified service technician to identify 

and repair the problem.

Diagnostic Description

Green LED Red LED

Control Fault (No Power)

Off

Off

L1/Neutral Polarity Fault

Flash

Flash

1 Hour Lockout

Alternating Flash

Normal Operation

On

On

Pressure Switch Closed Fault

On

Flash

Pressure Switch Open Fault

Flash

On

Open Limit Switch Fault

Flash

Off

Motor Fault

On

Off

Diagnostic Description

Yellow LED

Low Flame Sensor Signal

Continuous Flash

Flame Present

On

Table 6. Control Board Fault Conditions

TROUBLESHOOTING

DESCRIPTION OF COMPONENTS

The descriptions below are various functional components 
that affect the operation and shutting down of this furnace. 
Some of these components and their locations are shown 
in Figure 17. If any component of the furnace must be 
replaced, use only factory authorized replacement parts 
specified in the Replacement Parts List provided online.

Blower Limit Switch:

 Prevents operation when blower 

is not operational.

Flame Sensor: 

Verifies when a flame has carried over 

from the igniter to the opposite end burner. If no flame is 
detected, the furnace will shut down within 4 seconds.

Flame Roll-Out Switch:

 Verifies that the burner flames 

are drawn into the heat exchanger tubes. If the burner 
flames are not properly drawn into the heat exchanger, the 
flame roll-out switch will close the gas valve and initiate 
the shutdown cycle.

Gas Valve: 

Controls the flow of gas to the burners. When 

the  gas  valve  is  energized  it  automatically  opens  and 
regulates the gas pressure in the manifold.

Inducer  Assembly: 

Vents  products  of  combustion  to 

the outside.

Pressure  Switch: 

Verifies  that  the  inducer  is  drawing 

the combustion gases through the heat exchanger. The 
pressure switch prevents furnace operation with excessive 
flue/condensate blockage or improper inducer operation.

Main  Air  Limit  Switch:

  Prevents  the  air  temperature 

leaving the furnace from exceeding the maximum allowable 
outlet air temperature.

Figure 17. Furnace Components

Blower Assembly

Inducer Assembly

Gas Valve

Gas Manifold &
Burner Assembly

ON / OFF Switch

Control Board

Limit Switch

Inline Drain

Assembly

24V Transformer

Igniter

Main Air Limit Switch

Flame Sensor
Roll-Out Switch

Combustion Air Pipe

Exhaust Vent Pipe

Содержание CMF95 Series

Страница 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respec...

Страница 2: ...Base 13 MA 100 Universal Base Installation 14 Installing the Furnace on an MA 100 Base 15 Condensate Drainage 15 GAS SUPPLY PIPING 16 Leak Check 16 High Altitude Application 17 Converting to LP Propan...

Страница 3: ...ersonal injury or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code ANSI Z223 1 NFPA...

Страница 4: ...uses the appliance orequipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used andifapplicable aproduct approvedairintakemust be us...

Страница 5: ...tworkshouldbeappropriatelysizedtothecapacity of the furnace to ensure its proper airflow rating For installations above 2 000 ft the furnace should have a sea level input rating large enough that it w...

Страница 6: ...SSEMENT RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONED Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l emp...

Страница 7: ...t be known When estimating the length of vent runs consideration must be made to the effect of elbows and other fittings This is conveniently handled using the idea of equivalent length Thismeansthefi...

Страница 8: ...mination to windows and building air intakes Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes A vent terminal must be...

Страница 9: ...hown in Figure 4 The roof penetration mustbeproperlyflashedandwaterproofedwithaplumbing roof boot or equivalent flashing Vent and combustion air piping may be installed in an existing chimney which is...

Страница 10: ...I VentilAire IV Figure 5 VentilAire III IV Vent Freezing Protection CAUTION When the vent pipe is exposed to temperatures below freezing i e when it passes through unheated spaces chimneys etc the pip...

Страница 11: ...vent leakage It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant Requirements for sealing ducts vary from region to region Consult with local co...

Страница 12: ...CAUTION HAZARD OF ASPHYXIATION DO NOT COVER OR RESTRICT FLOOR RETURN AIR OPENING or equivalent For closet installation with less than 6 front clearance but not less than 1 a louvered door must be used...

Страница 13: ...fastenthefrontofthefurnace and the base to the floor with 8 x 1 2 sheet metal screws FURNACE INSTALLATION NOTE Sinceallinstallationsaredifferent thesequenceof these steps may differ from the actual in...

Страница 14: ...opening and center the top of the feeder duct in 14 1 8 x 14 1 8 floor opening 5 Using the feeder duct as a guide mark and cut a 12 x 12 opening in the supply duct Remove the base and transition feede...

Страница 15: ...will cause improper operation or damage to the furnace It is recommended that all drain lines on the outside of the residence be wrapped with an industry approved insulation or material allowed by loc...

Страница 16: ...l gas hookups are shown in Figure 12 Leak Check FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be pe...

Страница 17: ...nstallation may only be accomplished withfactorysuppliedorifices Donotattemptto drill out orifices in the field Improperly drilled orifices may cause fire explosion carbon monoxide poisoning personal...

Страница 18: ...ple Elevation 5 000 feet Type of Gas Natural Gas Local Heating Value of Gas 750 From Table 10 find 750 and follow down the column stop at the 5 000 feet row The heating value listed is LOW Table 12 wi...

Страница 19: ...ten until snug Make sure LP is visible after conversion Gas Pressure Verification Measuring the Supply Gas Pressure 1 Turn OFF the gas supply at the manual valve located on the outside of the unit 2 U...

Страница 20: ...are lit check all gas connections for leaks again with the soap and water solution Measuring the Manifold Pressure The manifold pressure must be measured by installing a pressure gauge Manometer Magn...

Страница 21: ...tothefurnace nameplate or Table 4 An electrical disconnect must be installed readily accessiblefromandlocatedwithinsightofthefurnace See Figure 18 page 29 or the wiring diagram label inside of the con...

Страница 22: ...otection2 045 45 000 18 115 60 1 127 103 11 0 14 20 13 1 21 7 072 72 000 18 115 60 1 127 103 10 4 14 20 12 4 20 4 NOTE Minimum wire gauge and maximum fuse circuit breaker amperage are based on MCA1 an...

Страница 23: ...e input rate in Btuh See example 6 The manifold pressure must be set to the appropriate valueforeachinstallationbyaqualifiedinstaller service agency or the gas supplier WARNING Do not attempt to drill...

Страница 24: ...nutes before taking any temperature readings The temperature rise is the difference between the supply and return air temperatures Verifying Burner Operation CAUTION The door over the burners may only...

Страница 25: ...alve and inducer remains energized The control goes to blower on delay 8 If flame is present the control energizes the blower on theselectedHEATspeed30secondsafterthegasvalve opened The gas valve and...

Страница 26: ...piping at the furnace 6 Remove the piping between the gas valve and the ground joint union If applicable 7 Remove the burner box door 6 screws 8 Remove 4 screws securing the manifold assembly to the b...

Страница 27: ...Fault Flash On Open Limit Switch Fault Flash Off Motor Fault On Off Diagnostic Description Yellow LED Low Flame Sensor Signal Continuous Flash Flame Present On Table 6 Control Board Fault Conditions...

Страница 28: ...8 1 3 8 1 5 8 24 3 16 4 3 4 2 7 8 1 3 4 1 3 4 16 1 2 13 5 8 3 1 2 X 1 1 2 Slots for Gas Pipe Condensate drains Typ FRONT VIEW LEFT SIDE TOP VIEW BOTTOM VIEW 3 3 4 Dia 2 Places 32 2 7 8 Dia Hole for Li...

Страница 29: ...SINGLE STAGE THERMOSTAT TO OUTDOOR UNIT FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM For 80 and 90 Single Stage Furnaces Refer to the Installation Instructions provided with the furnac...

Страница 30: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Страница 31: ...T BTU 45 000 72 000 0 to 1 999 FT 49 47 2 000 to 2 999 FT 50 48 3 000 to 3 999 FT 50 48 4 000 to 4 999 FT 51 48 5 000 to 5 999 FT 51 49 6 000 to 6 999 FT 51 49 7 000 to 7 999 FT 52 50 8 000 to 8 999 F...

Страница 32: ...ls All Clearances in this Figure apply on both walls G Clearance to inside corner All Clearances in this Figure apply on both walls All Clearances in this Figure apply on both walls H Clearance to eac...

Страница 33: ...ble Wall Normal Snow Level COMBUSTION AIR Seal Caulk Around Pipes at Building 90 Elbow 7 12 Min 90 Elbow 90 Elbow Support System on Vertical Rise FLUE PIPE COMBUSTION AIR See Table 2 for PVC Pipe Leng...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...efully before starting the installation Return these instructions to the customer s package for future reference PROPOSITION 65 WARNING This product contains chemicals known to the state of California...

Отзывы: