COMBUSTION AIR & VENTING REQUIREMENTS 

 WARNING:

CARBON MONOXIDE POISONING HAZARD

Failure  to  follow  the  steps  outlined  below  for 

each appliance connected to the venting system 
being placed into operation could result in carbon 
monoxide poisoning or death. The following steps 
shall be followed with each individual appliance 
connected to the venting system being placed in 
operation, while all other appliances connected to 
the venting system are not in operation:

1. Seal  any  unused  openings  in  the  venting 

system.

2. Inspect the venting system for proper size and 

horizontal pitch, as required in the National Fuel 

Gas  Code,  ANSI  Z223.1/NFPA  54  or  the  CSA 

B149.1, Natural Gas and Propane Installation 

Codes and these instructions. Determine that 

there  is  no  blockage  or  restriction,  leakage, 

corrosion and other deficiencies which could 

cause an unsafe condition.

3. As far as practical, close all building doors and 

windows and all doors between the space in 

which the appliance(s) connected to the venting 

system  are  located  and  other  spaces  of  the 

building.

4. Close fireplace dampers.

5. Turn  on  clothes  dryers  and  any  appliance 

not connected to the venting system. Turn on 

any  exhaust  fans,  such  as  range  hoods  and 

bathroom exhausts, so they are operating at 

maximum  speed.  Do  not  operate  a  summer 

exhaust fan.

6. Follow  the  lighting  instructions.  Place  the 

appliance  being  inspected  into  operation. 

Adjust the thermostat so appliance is operating 

continuously.

7. Test  for  spillage  from  draft  hood  equipped 

appliances  at  the  draft  hood  relief  opening 

after 5 minutes of main burner operation. Use 

the flame of a match or candle.

8. If improper venting is observed during any of 

the above tests, the venting system must be 

corrected in accordance with the National Fuel 

Gas Code, ANSI Z223.1/NFPA 54 and/or CSA 

B149.1, Natural Gas and Propane Installation 

Codes.

9. After it has been determined that each appliance 

connected to the venting system properly vents 

when tested as outlined above, return doors, 

windows, exhaust fans, fireplace dampers and 

any other gas-fired burning appliance to their 

previous conditions of use.

 AVERTISSEMENT:

RISQUE D’EMPOISONNEMENT AU 

MONOXYDE DE CARBONED

Le  non-respect  des  consignes  suivantes  portant 

sur  chacun  des  appareils  raccordés  au  système 

d’évacuation  mis  en  service  pourrait  entraîner 

l’empoisennement  au  monoxyde  de  carbone  ou 

la  mort.  Les  consignes  suivantes  doivent  être 

observées pour chaque appareil raccordé au système 

d’évacuation mis en service si les autres appareils 

raccordés au système ne sont pas en service:

1. Sceller toute ouverture non utilisée de la systéme 

d’évacuation;

2. S’assurer que la systéme d’évacuation présente 

des  dimensions  et  une  pente  horizontale 

conformes  à  la  norme  ANSI  Z223.1/NFPA 

54,  intitulée  National  Fuel  Gas  Code  ou  aux 

codes  d’installation  CSA-B149.1,  ainsi  qu’aux 

présentes instructions. S’assurer que la systéme 

d’évacuation  n’est  pas  bloquée,  restreinte, 

corrodée, qu’elle ne fuit pas et qu’elle ne présente 

aucun autre défaut potentiellement dangereux;

3. Dans la mesure du possible, fermer toutes les 

portes et fenêtres du bâtiment, et toutes les portes 

entre la pièce où se trouve l’appareil raccordé à 

la systéme d’évacuation et les autres pièces du 

bâtiment.

4. Fermer les registres des foyers;

5. Mettre  en  service  les  sécheuses  et  tout  autre 

appareil  qui  n’est  pas  raccordé  à  la  systéme 

d’évacuation. Faire fonctionner à régime maximal 

tout ventilateur d’évacuation, tel que les hottes de 

cuisinière et les ventilateurs de salles de bains. 

Ne pas mettre en service les ventilateurs d’été.

6. Respecter les instructions d’allumage. Mettre en 

service l’appareil à l’essai. Régler le thermostat 

de manière à ce que l’appareil fonctionne sans 

interruption;

7. Vérifier  s’il  y  a  débordement  à  l’orifice 

d’évacuation du coupe tirage des appareils dotés 

d’un  coupe  tirage  5  minutes  après  l’allumage 

du  brûleur  principal.  Utiliser  la  flamme  d’une 

allumette ou d’une chandelle.

8. Si  l’on  constate,  au  cours  de  l’un  des  essais 

qui  précèdent,  que  l’évacuation  est  déficiente, 

corriger le système d’évacuation conformément 

à  la  norm  ANSI  Z223.1/NFPA  54,  National  Fuel 

Gas Code, et (ou) aux codes d’installation CSA 

B149.1.

9. Après  avoir  déterminé  que  tous  les  appareils 

raccordés à la systéme d’évacuation évacuent 

correctement  tel  que  prescrit  ci-dessus, 

rouvrir les portes et les fenêtres et remettre les 

ventilateurs d’évacuation, les registres de foyers 

et tout autre appareil fonctionnant au gaz à leur 

état de fonctionnement initial.

Содержание CMF95 Series

Страница 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respec...

Страница 2: ...Base 13 MA 100 Universal Base Installation 14 Installing the Furnace on an MA 100 Base 15 Condensate Drainage 15 GAS SUPPLY PIPING 16 Leak Check 16 High Altitude Application 17 Converting to LP Propan...

Страница 3: ...ersonal injury or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code ANSI Z223 1 NFPA...

Страница 4: ...uses the appliance orequipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used andifapplicable aproduct approvedairintakemust be us...

Страница 5: ...tworkshouldbeappropriatelysizedtothecapacity of the furnace to ensure its proper airflow rating For installations above 2 000 ft the furnace should have a sea level input rating large enough that it w...

Страница 6: ...SSEMENT RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONED Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l emp...

Страница 7: ...t be known When estimating the length of vent runs consideration must be made to the effect of elbows and other fittings This is conveniently handled using the idea of equivalent length Thismeansthefi...

Страница 8: ...mination to windows and building air intakes Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes A vent terminal must be...

Страница 9: ...hown in Figure 4 The roof penetration mustbeproperlyflashedandwaterproofedwithaplumbing roof boot or equivalent flashing Vent and combustion air piping may be installed in an existing chimney which is...

Страница 10: ...I VentilAire IV Figure 5 VentilAire III IV Vent Freezing Protection CAUTION When the vent pipe is exposed to temperatures below freezing i e when it passes through unheated spaces chimneys etc the pip...

Страница 11: ...vent leakage It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant Requirements for sealing ducts vary from region to region Consult with local co...

Страница 12: ...CAUTION HAZARD OF ASPHYXIATION DO NOT COVER OR RESTRICT FLOOR RETURN AIR OPENING or equivalent For closet installation with less than 6 front clearance but not less than 1 a louvered door must be used...

Страница 13: ...fastenthefrontofthefurnace and the base to the floor with 8 x 1 2 sheet metal screws FURNACE INSTALLATION NOTE Sinceallinstallationsaredifferent thesequenceof these steps may differ from the actual in...

Страница 14: ...opening and center the top of the feeder duct in 14 1 8 x 14 1 8 floor opening 5 Using the feeder duct as a guide mark and cut a 12 x 12 opening in the supply duct Remove the base and transition feede...

Страница 15: ...will cause improper operation or damage to the furnace It is recommended that all drain lines on the outside of the residence be wrapped with an industry approved insulation or material allowed by loc...

Страница 16: ...l gas hookups are shown in Figure 12 Leak Check FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be pe...

Страница 17: ...nstallation may only be accomplished withfactorysuppliedorifices Donotattemptto drill out orifices in the field Improperly drilled orifices may cause fire explosion carbon monoxide poisoning personal...

Страница 18: ...ple Elevation 5 000 feet Type of Gas Natural Gas Local Heating Value of Gas 750 From Table 10 find 750 and follow down the column stop at the 5 000 feet row The heating value listed is LOW Table 12 wi...

Страница 19: ...ten until snug Make sure LP is visible after conversion Gas Pressure Verification Measuring the Supply Gas Pressure 1 Turn OFF the gas supply at the manual valve located on the outside of the unit 2 U...

Страница 20: ...are lit check all gas connections for leaks again with the soap and water solution Measuring the Manifold Pressure The manifold pressure must be measured by installing a pressure gauge Manometer Magn...

Страница 21: ...tothefurnace nameplate or Table 4 An electrical disconnect must be installed readily accessiblefromandlocatedwithinsightofthefurnace See Figure 18 page 29 or the wiring diagram label inside of the con...

Страница 22: ...otection2 045 45 000 18 115 60 1 127 103 11 0 14 20 13 1 21 7 072 72 000 18 115 60 1 127 103 10 4 14 20 12 4 20 4 NOTE Minimum wire gauge and maximum fuse circuit breaker amperage are based on MCA1 an...

Страница 23: ...e input rate in Btuh See example 6 The manifold pressure must be set to the appropriate valueforeachinstallationbyaqualifiedinstaller service agency or the gas supplier WARNING Do not attempt to drill...

Страница 24: ...nutes before taking any temperature readings The temperature rise is the difference between the supply and return air temperatures Verifying Burner Operation CAUTION The door over the burners may only...

Страница 25: ...alve and inducer remains energized The control goes to blower on delay 8 If flame is present the control energizes the blower on theselectedHEATspeed30secondsafterthegasvalve opened The gas valve and...

Страница 26: ...piping at the furnace 6 Remove the piping between the gas valve and the ground joint union If applicable 7 Remove the burner box door 6 screws 8 Remove 4 screws securing the manifold assembly to the b...

Страница 27: ...Fault Flash On Open Limit Switch Fault Flash Off Motor Fault On Off Diagnostic Description Yellow LED Low Flame Sensor Signal Continuous Flash Flame Present On Table 6 Control Board Fault Conditions...

Страница 28: ...8 1 3 8 1 5 8 24 3 16 4 3 4 2 7 8 1 3 4 1 3 4 16 1 2 13 5 8 3 1 2 X 1 1 2 Slots for Gas Pipe Condensate drains Typ FRONT VIEW LEFT SIDE TOP VIEW BOTTOM VIEW 3 3 4 Dia 2 Places 32 2 7 8 Dia Hole for Li...

Страница 29: ...SINGLE STAGE THERMOSTAT TO OUTDOOR UNIT FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM For 80 and 90 Single Stage Furnaces Refer to the Installation Instructions provided with the furnac...

Страница 30: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Страница 31: ...T BTU 45 000 72 000 0 to 1 999 FT 49 47 2 000 to 2 999 FT 50 48 3 000 to 3 999 FT 50 48 4 000 to 4 999 FT 51 48 5 000 to 5 999 FT 51 49 6 000 to 6 999 FT 51 49 7 000 to 7 999 FT 52 50 8 000 to 8 999 F...

Страница 32: ...ls All Clearances in this Figure apply on both walls G Clearance to inside corner All Clearances in this Figure apply on both walls All Clearances in this Figure apply on both walls H Clearance to eac...

Страница 33: ...ble Wall Normal Snow Level COMBUSTION AIR Seal Caulk Around Pipes at Building 90 Elbow 7 12 Min 90 Elbow 90 Elbow Support System on Vertical Rise FLUE PIPE COMBUSTION AIR See Table 2 for PVC Pipe Leng...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...efully before starting the installation Return these instructions to the customer s package for future reference PROPOSITION 65 WARNING This product contains chemicals known to the state of California...

Отзывы: