background image

4

1. For  direct-vent  appliances,  mechanical-vent  heating 

appliances or domestic hot water equipment, where the 
bottom of the vent terminal and the air intake is installed 
below four feet above grade the following requirements 
must be satisfied:

a.) A carbon monoxide (CO) detector and alarm shall be 

placed on each floor level where there are bedrooms. 
The  detector  shall  comply  with  NFPA  720  (2005 
Edition) and be mounted in the living area outside 
the bedroom(s).

b.) A (CO) detector shall be located in the room that 

houses the appliance or equipment and shall:

• Be powered by the same electrical circuit as the 

appliance or equipment. Only one service switch 
shall power the appliance and the (CO) detector;

• Have battery back-up power;
• Meet ANSI/UL 2034 Standards and comply with 

NFPA 720 (2005 Edition); and Approved and listed 
by a Nationally Recognized Testing Laboratory as 
recognized under 527 CMR.

c.) A Product-approved vent terminal must be used, 

and if applicable, a product-approved air intake must 
be used. Installation shall be in strict compliance 
with  the  manufacturer’s  instructions.  A  copy  of 
the  installation  instructions  shall  remain  with  the 
appliance  or  equipment  at  the  completion  of  the 
installation.

d.) A metal or plastic identification plate shall be mounted 

at the exterior of the building, 4 feet directly above 
the location of vent terminal. The plate shall be of 
sufficient size, easily read from a distance of eight 
feet away, and read “Gas Vent Directly Below”.

2. For  direct-vent  appliances,  mechanical  vent  heating 

appliances or domestic hot water equipment where the 
bottom of the vent terminal and the air intake is installed 
above four feet above grade the following requirements 
must be satisfied:

a.) A (CO) detector and alarm shall be placed on each 

floor level where there are bedrooms. The detector 
shall comply with NFPA 720 (2005 Edition) and be 
mounted in the living area outside the bedroom(s).

b.) The (CO) detector shall:

• Be located in the room that houses the appliance 

or equipment;

• Be hard-wired, battery powered or both.
• Shall comply with NFPA 720 (2005 Edition).

c.) A  product-approved  vent  terminal  must  be  used, 

and if applicable, a product-approved air intake must 
be used. Installation shall be in strict compliance 
with  the  manufacturer’s  instructions.  A  copy  of 
the  installation  instructions  shall  remain  with  the 
appliance  or  equipment  at  the  completion  of  the 
installation.

The information listed below is for reference purposes only 
and does not necessarily have jurisdiction over local or state 
codes. Always consult with local authorities before installing 
any gas appliance.

Combustion & Ventilation Air

•  US: National Fuel Gas Code (NFGC/ NFPA-54), Air for 

Combustion and Ventilation

•  CANADA: Natural Gas and Propane Installation Codes 

(NSCNGPIC),  Venting  Systems  and  Air  Supply  for 

Appliances

Duct Systems

•  US and CANADA: Air Conditioning Contractors Association 

(ACCA) Manual D, Sheet Metal and Air Conditioning - 

National Association (SMACNA), or American Society of 

Heating, Refrigeration, and Air Conditioning Engineers 

(ASHRAE) Fundamentals Handbook

Electrical Connections

•  US: National Electrical Code (NEC) ANSI/NFPA 70

•  CANADA: Canadian Electrical Code CSA C22.1

Gas Piping & Gas Pipe Pressure Testing

•  US: NFGC and National Plumbing Codes

•  CANADA: NSCNGPIC

•  American National Standard (NFPA-54) and/or CAN/CSA 

B149 for all gas-fired furnace models.

General Installation

•  US: Current edition of the NFGC and the NFPA 90B. For 

copies, contact the National Fire Protection Association 

Inc., Batterymarch Park, Quincy, MA 02269; or American 

Gas Association, 400 N. Capitol, N.W., Washington DC 

20001 or www.NFPA.org

•  CANADA: NSCNGPIC. For a copy, contact Standard Sales, 

CSA  International,  178  Rexdale  Boulevard,  Etobicoke 

(Toronto), Ontario, M9W 1R3 Canada

•  Federal  Manufactured  Home  Constructions  &  Safety 

Standard (H.U.D. Title 24, Part 3280.707[a][2])

•  American National Standard (ANSI-119.2/NFPA-501C) 

for all recreational vehicle installations.

Safety

•  US: (NFGC) ANSI Z223.1 /NFPA 54 and the Installation 

Standards,  Warm  Air  Heating  and  Air  Conditioning 

Systems ANSI/NFPA 90B.

•  CANADA:  CAN/CGA-B149.1  and  .2–M00  National 

Standard of Canada. (NSCNGPIC)

Содержание CMF95 Series

Страница 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respec...

Страница 2: ...Base 13 MA 100 Universal Base Installation 14 Installing the Furnace on an MA 100 Base 15 Condensate Drainage 15 GAS SUPPLY PIPING 16 Leak Check 16 High Altitude Application 17 Converting to LP Propan...

Страница 3: ...ersonal injury or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code ANSI Z223 1 NFPA...

Страница 4: ...uses the appliance orequipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used andifapplicable aproduct approvedairintakemust be us...

Страница 5: ...tworkshouldbeappropriatelysizedtothecapacity of the furnace to ensure its proper airflow rating For installations above 2 000 ft the furnace should have a sea level input rating large enough that it w...

Страница 6: ...SSEMENT RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONED Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l emp...

Страница 7: ...t be known When estimating the length of vent runs consideration must be made to the effect of elbows and other fittings This is conveniently handled using the idea of equivalent length Thismeansthefi...

Страница 8: ...mination to windows and building air intakes Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes A vent terminal must be...

Страница 9: ...hown in Figure 4 The roof penetration mustbeproperlyflashedandwaterproofedwithaplumbing roof boot or equivalent flashing Vent and combustion air piping may be installed in an existing chimney which is...

Страница 10: ...I VentilAire IV Figure 5 VentilAire III IV Vent Freezing Protection CAUTION When the vent pipe is exposed to temperatures below freezing i e when it passes through unheated spaces chimneys etc the pip...

Страница 11: ...vent leakage It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant Requirements for sealing ducts vary from region to region Consult with local co...

Страница 12: ...CAUTION HAZARD OF ASPHYXIATION DO NOT COVER OR RESTRICT FLOOR RETURN AIR OPENING or equivalent For closet installation with less than 6 front clearance but not less than 1 a louvered door must be used...

Страница 13: ...fastenthefrontofthefurnace and the base to the floor with 8 x 1 2 sheet metal screws FURNACE INSTALLATION NOTE Sinceallinstallationsaredifferent thesequenceof these steps may differ from the actual in...

Страница 14: ...opening and center the top of the feeder duct in 14 1 8 x 14 1 8 floor opening 5 Using the feeder duct as a guide mark and cut a 12 x 12 opening in the supply duct Remove the base and transition feede...

Страница 15: ...will cause improper operation or damage to the furnace It is recommended that all drain lines on the outside of the residence be wrapped with an industry approved insulation or material allowed by loc...

Страница 16: ...l gas hookups are shown in Figure 12 Leak Check FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be pe...

Страница 17: ...nstallation may only be accomplished withfactorysuppliedorifices Donotattemptto drill out orifices in the field Improperly drilled orifices may cause fire explosion carbon monoxide poisoning personal...

Страница 18: ...ple Elevation 5 000 feet Type of Gas Natural Gas Local Heating Value of Gas 750 From Table 10 find 750 and follow down the column stop at the 5 000 feet row The heating value listed is LOW Table 12 wi...

Страница 19: ...ten until snug Make sure LP is visible after conversion Gas Pressure Verification Measuring the Supply Gas Pressure 1 Turn OFF the gas supply at the manual valve located on the outside of the unit 2 U...

Страница 20: ...are lit check all gas connections for leaks again with the soap and water solution Measuring the Manifold Pressure The manifold pressure must be measured by installing a pressure gauge Manometer Magn...

Страница 21: ...tothefurnace nameplate or Table 4 An electrical disconnect must be installed readily accessiblefromandlocatedwithinsightofthefurnace See Figure 18 page 29 or the wiring diagram label inside of the con...

Страница 22: ...otection2 045 45 000 18 115 60 1 127 103 11 0 14 20 13 1 21 7 072 72 000 18 115 60 1 127 103 10 4 14 20 12 4 20 4 NOTE Minimum wire gauge and maximum fuse circuit breaker amperage are based on MCA1 an...

Страница 23: ...e input rate in Btuh See example 6 The manifold pressure must be set to the appropriate valueforeachinstallationbyaqualifiedinstaller service agency or the gas supplier WARNING Do not attempt to drill...

Страница 24: ...nutes before taking any temperature readings The temperature rise is the difference between the supply and return air temperatures Verifying Burner Operation CAUTION The door over the burners may only...

Страница 25: ...alve and inducer remains energized The control goes to blower on delay 8 If flame is present the control energizes the blower on theselectedHEATspeed30secondsafterthegasvalve opened The gas valve and...

Страница 26: ...piping at the furnace 6 Remove the piping between the gas valve and the ground joint union If applicable 7 Remove the burner box door 6 screws 8 Remove 4 screws securing the manifold assembly to the b...

Страница 27: ...Fault Flash On Open Limit Switch Fault Flash Off Motor Fault On Off Diagnostic Description Yellow LED Low Flame Sensor Signal Continuous Flash Flame Present On Table 6 Control Board Fault Conditions...

Страница 28: ...8 1 3 8 1 5 8 24 3 16 4 3 4 2 7 8 1 3 4 1 3 4 16 1 2 13 5 8 3 1 2 X 1 1 2 Slots for Gas Pipe Condensate drains Typ FRONT VIEW LEFT SIDE TOP VIEW BOTTOM VIEW 3 3 4 Dia 2 Places 32 2 7 8 Dia Hole for Li...

Страница 29: ...SINGLE STAGE THERMOSTAT TO OUTDOOR UNIT FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM For 80 and 90 Single Stage Furnaces Refer to the Installation Instructions provided with the furnac...

Страница 30: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Страница 31: ...T BTU 45 000 72 000 0 to 1 999 FT 49 47 2 000 to 2 999 FT 50 48 3 000 to 3 999 FT 50 48 4 000 to 4 999 FT 51 48 5 000 to 5 999 FT 51 49 6 000 to 6 999 FT 51 49 7 000 to 7 999 FT 52 50 8 000 to 8 999 F...

Страница 32: ...ls All Clearances in this Figure apply on both walls G Clearance to inside corner All Clearances in this Figure apply on both walls All Clearances in this Figure apply on both walls H Clearance to eac...

Страница 33: ...ble Wall Normal Snow Level COMBUSTION AIR Seal Caulk Around Pipes at Building 90 Elbow 7 12 Min 90 Elbow 90 Elbow Support System on Vertical Rise FLUE PIPE COMBUSTION AIR See Table 2 for PVC Pipe Leng...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...efully before starting the installation Return these instructions to the customer s package for future reference PROPOSITION 65 WARNING This product contains chemicals known to the state of California...

Отзывы: