background image

26

•  To  achieve  the  best  performance  and  minimize 

equipment  failure  it  is  recommended  that  a  yearly 

maintenance checkup be performed. At a minimum, 

this check should include the following items:

Air Filter(s)

 WARNING:

Never  operate  the  furnace  without  a  filter  in 
place.  Dust  and  lint  can  build  up  on  internal 
components,  resulting  in  loss  of  efficiency, 
equipment damage, and possible fire.

An air filter is supplied with the furnace as shipped from 
the factory. Filters should be changed or cleaned monthly 
during the heating season. Newly built or renovated homes 
may require more frequent changing until the construction 
dust has minimized.

Filters  designed  to  remove  smaller  particles  such  as 
pollen, may require additional maintenance.

Blower Compartment

Dirt  and  lint  can  create  excessive  loads  on  the  motor 
resulting in higher than normal operating temperatures 
and shortened service life. It is recommended that the 
blower compartment be cleaned of dirt or lint that may 
have accumulated in the compartment or on the blower 
and motor as part of the annual inspection.

Cleaning of Burners

If the burners must be cleaned, follow steps 1-12. See 
Figure 17 (page 27) for component location.
1. Shut off gas supply to the furnace at the meter or at a 

manual valve in the supply piping.

2. Turn off all power to the furnace and set the thermostat 

to it’s lowest setting.

3. Turn  the  gas  control  knob  to  the  OFF  position.  See 

Figure 13 (page 18).

4. Disconnect the wires from the gas valve, igniter, flame 

sensor, and flame rollout switch.

 CAUTION:

To  prevent  damage  to  the  unit  or  internal 
components,  it  is  recommended  that  two 
wrenches be used when loosening or tightening 
nuts. Do not over tighten!

5. Using two wrenches, separate the ground-joint union 

in the gas supply piping at the furnace.

6. Remove  the  piping  between  the  gas  valve  and  the 

ground-joint union. (If applicable).

7. Remove the burner box door (6 screws).
8. Remove 4 screws securing the manifold assembly to 

the burner box.

9. Remove  4  screws  from  the  corners  of  the  box  and 

carefully remove the burner assembly from the furnace.

  

IMPORTANT:  DO  NOT  damage  the  igniter  while 
removing the burner assembly.

10. Inspect the burners for accumulated dust or debris. 

If  necessary  carefully  clean  them  with  a  soft  wire 
brush and a vacuum cleaner. 

IMPORTANT:

 

DO NOT 

damage  the  igniter  while  cleaning  the  burner 
assembly.

11. Replace all the parts in reverse order that they were 

removed.

12. Follow the lighting instructions found on the furnace 

door to return the furnace to operation. Verify proper 
operation after servicing.

Vent System

 WARNING:

Holes in the vent pipe or heat exchanger can 
cause combustion products to enter the home. 
Replace the vent pipe or heat exchanger if leaks 
are  found.  Failure  to  prevent  the  circulation 
of combustion products into the living space 
can  create  potentially  hazardous  conditions 
including  carbon  monoxide  poisoning  that 
could result in personal injury or death.

Check the inlet pipe (if applicable) and outlet pipe to ensure 
they  are  not  blocked  by  debris.  Any  damaged  section 
of vent pipe must be replaced, and any obstruction or 
blockage must be removed prior to operating the furnace.

Heat Exchanger & Burner Maintenance

The furnace should operate for many years without soot 
buildup in the flue passageways, however, the flue, vent 
system, and burners should be inspected and cleaned 
(if required) by a qualified service technician annually to 
ensure  continued  safe  operation.  Pay  attention  to  any 
deterioration from corrosion or other sources.

Lubrication

The bearings in the blower motor and inducer blower used 
in these furnaces are pre-lubricated and sealed by the 
manufacturer. No further oiling of the bearings is required 
for the life of the motor.

Содержание CMF95 Series

Страница 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respec...

Страница 2: ...Base 13 MA 100 Universal Base Installation 14 Installing the Furnace on an MA 100 Base 15 Condensate Drainage 15 GAS SUPPLY PIPING 16 Leak Check 16 High Altitude Application 17 Converting to LP Propan...

Страница 3: ...ersonal injury or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code ANSI Z223 1 NFPA...

Страница 4: ...uses the appliance orequipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used andifapplicable aproduct approvedairintakemust be us...

Страница 5: ...tworkshouldbeappropriatelysizedtothecapacity of the furnace to ensure its proper airflow rating For installations above 2 000 ft the furnace should have a sea level input rating large enough that it w...

Страница 6: ...SSEMENT RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONED Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l emp...

Страница 7: ...t be known When estimating the length of vent runs consideration must be made to the effect of elbows and other fittings This is conveniently handled using the idea of equivalent length Thismeansthefi...

Страница 8: ...mination to windows and building air intakes Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes A vent terminal must be...

Страница 9: ...hown in Figure 4 The roof penetration mustbeproperlyflashedandwaterproofedwithaplumbing roof boot or equivalent flashing Vent and combustion air piping may be installed in an existing chimney which is...

Страница 10: ...I VentilAire IV Figure 5 VentilAire III IV Vent Freezing Protection CAUTION When the vent pipe is exposed to temperatures below freezing i e when it passes through unheated spaces chimneys etc the pip...

Страница 11: ...vent leakage It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant Requirements for sealing ducts vary from region to region Consult with local co...

Страница 12: ...CAUTION HAZARD OF ASPHYXIATION DO NOT COVER OR RESTRICT FLOOR RETURN AIR OPENING or equivalent For closet installation with less than 6 front clearance but not less than 1 a louvered door must be used...

Страница 13: ...fastenthefrontofthefurnace and the base to the floor with 8 x 1 2 sheet metal screws FURNACE INSTALLATION NOTE Sinceallinstallationsaredifferent thesequenceof these steps may differ from the actual in...

Страница 14: ...opening and center the top of the feeder duct in 14 1 8 x 14 1 8 floor opening 5 Using the feeder duct as a guide mark and cut a 12 x 12 opening in the supply duct Remove the base and transition feede...

Страница 15: ...will cause improper operation or damage to the furnace It is recommended that all drain lines on the outside of the residence be wrapped with an industry approved insulation or material allowed by loc...

Страница 16: ...l gas hookups are shown in Figure 12 Leak Check FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be pe...

Страница 17: ...nstallation may only be accomplished withfactorysuppliedorifices Donotattemptto drill out orifices in the field Improperly drilled orifices may cause fire explosion carbon monoxide poisoning personal...

Страница 18: ...ple Elevation 5 000 feet Type of Gas Natural Gas Local Heating Value of Gas 750 From Table 10 find 750 and follow down the column stop at the 5 000 feet row The heating value listed is LOW Table 12 wi...

Страница 19: ...ten until snug Make sure LP is visible after conversion Gas Pressure Verification Measuring the Supply Gas Pressure 1 Turn OFF the gas supply at the manual valve located on the outside of the unit 2 U...

Страница 20: ...are lit check all gas connections for leaks again with the soap and water solution Measuring the Manifold Pressure The manifold pressure must be measured by installing a pressure gauge Manometer Magn...

Страница 21: ...tothefurnace nameplate or Table 4 An electrical disconnect must be installed readily accessiblefromandlocatedwithinsightofthefurnace See Figure 18 page 29 or the wiring diagram label inside of the con...

Страница 22: ...otection2 045 45 000 18 115 60 1 127 103 11 0 14 20 13 1 21 7 072 72 000 18 115 60 1 127 103 10 4 14 20 12 4 20 4 NOTE Minimum wire gauge and maximum fuse circuit breaker amperage are based on MCA1 an...

Страница 23: ...e input rate in Btuh See example 6 The manifold pressure must be set to the appropriate valueforeachinstallationbyaqualifiedinstaller service agency or the gas supplier WARNING Do not attempt to drill...

Страница 24: ...nutes before taking any temperature readings The temperature rise is the difference between the supply and return air temperatures Verifying Burner Operation CAUTION The door over the burners may only...

Страница 25: ...alve and inducer remains energized The control goes to blower on delay 8 If flame is present the control energizes the blower on theselectedHEATspeed30secondsafterthegasvalve opened The gas valve and...

Страница 26: ...piping at the furnace 6 Remove the piping between the gas valve and the ground joint union If applicable 7 Remove the burner box door 6 screws 8 Remove 4 screws securing the manifold assembly to the b...

Страница 27: ...Fault Flash On Open Limit Switch Fault Flash Off Motor Fault On Off Diagnostic Description Yellow LED Low Flame Sensor Signal Continuous Flash Flame Present On Table 6 Control Board Fault Conditions...

Страница 28: ...8 1 3 8 1 5 8 24 3 16 4 3 4 2 7 8 1 3 4 1 3 4 16 1 2 13 5 8 3 1 2 X 1 1 2 Slots for Gas Pipe Condensate drains Typ FRONT VIEW LEFT SIDE TOP VIEW BOTTOM VIEW 3 3 4 Dia 2 Places 32 2 7 8 Dia Hole for Li...

Страница 29: ...SINGLE STAGE THERMOSTAT TO OUTDOOR UNIT FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM For 80 and 90 Single Stage Furnaces Refer to the Installation Instructions provided with the furnac...

Страница 30: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Страница 31: ...T BTU 45 000 72 000 0 to 1 999 FT 49 47 2 000 to 2 999 FT 50 48 3 000 to 3 999 FT 50 48 4 000 to 4 999 FT 51 48 5 000 to 5 999 FT 51 49 6 000 to 6 999 FT 51 49 7 000 to 7 999 FT 52 50 8 000 to 8 999 F...

Страница 32: ...ls All Clearances in this Figure apply on both walls G Clearance to inside corner All Clearances in this Figure apply on both walls All Clearances in this Figure apply on both walls H Clearance to eac...

Страница 33: ...ble Wall Normal Snow Level COMBUSTION AIR Seal Caulk Around Pipes at Building 90 Elbow 7 12 Min 90 Elbow 90 Elbow Support System on Vertical Rise FLUE PIPE COMBUSTION AIR See Table 2 for PVC Pipe Leng...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...efully before starting the installation Return these instructions to the customer s package for future reference PROPOSITION 65 WARNING This product contains chemicals known to the state of California...

Отзывы: