background image

21

Line Voltage Wiring

•  Electrical connections must be in compliance with all 

applicable local codes with the current revision of the 

National Electric Code (ANSI/NFPA 70).

•  For Canadian installations the electrical connections 

and grounding shall comply with the current Canadian 

Electrical Code (CSA C22.1 and/or local codes).

•  It is recommended that the line voltage (115 VAC) to 

the furnace be supplied from a dedicated branch circuit 
containing the correct fuse or circuit breaker for the 
furnace as listed in Table 4 (page 22).

ELECTRICAL SHOCK, FIRE OR EXPLOSION 

HAZARD

Failure to follow safety warnings exactly could 
result in serious injury or property damage.
Improper servicing could result in dangerous 
operation,  serious  injury,  death  or  property 

damage.

•  Before  servicing,  disconnect  all  electrical 

power to furnace.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.”

 WARNING:

RISQUE DE CHOC ÉLECTRIQUE, D’INCENDIE 
OU D’EXPLOSION

Le  non-respect  des  avertissements  de  sécurité 

pourrait entraîner un fonctionnement dangereux 

de l’appareil, des blessures graves, la mort ou des 

dommages matériels.

Un  entretein  incorrect  pourrait  entraîner  un 

fonctionnement dangereux de l’appareil, des 

blessures graves, la mort ou des dommages 

matériels

•  Couper  toute  alimentation  électrique  au 

générateur d’air chaud avant de prodéder 

aux travaux d’entretein.

•  Au moment de l’entretien des commandes, 

étiquetez tous les fils avant de les débrancher. 

S’assurer de les raccorder correctement.

•  S’assurer  que  l’appareil  fonctionne 

adéquatement aprés l’entretien

.

 

AVERTISSEMENT

:

ELECTRICAL WIRING

IMPORTANT NOTES:

If replacing any of the original wires supplied with 
the  furnace,  the  replacement  wire  must  be  copper 
wiring and have a temperature rating of at least 105°F 
(40°C). For electrical specifications, refer to the furnace 
nameplate or Table 4.

An  electrical  disconnect  must  be  installed  readily 
accessible from and located within sight of the furnace. 
See Figure 18 (page 29) or the wiring diagram label 
inside of the control door. Any other wiring methods 
must be acceptable to authority having jurisdiction.

Proper  line  voltage  polarity  must  be  maintained  in 
order  for  the  control  system  to  operate  correctly. 
Verify the incoming neutral line is connected to the 
white wire and the incoming HOT line is connected 
to the black wire. The furnace will not operate unless 
the polarity and ground are properly connected as 
shown in Figure 18.

Grounding

 WARNING:

To minimize personal injury, the furnace cabinet 
must  have  an  uninterrupted  or  unbroken 
electrical  ground.  The  controls  used  in  this 
furnace  require  an  earth  ground  to  operate 
properly. Acceptable methods include electrical 
wire or conduit approved for ground service. 
Do not use gas piping as an electrical ground!

Thermostat / Low Voltage Connections

•  The furnace is designed to be controlled by a 24 VAC 

thermostat. The thermostat’s wiring must comply with 

the current provisions of the NEC (ANSI/NFPA 70) and 

with applicable local codes having jurisdiction.

•  The  thermostat  must  be  installed  according  to  the 

instructions supplied by the thermostat manufacturer. 

Low voltage connections (24 VAC) from the thermostat 

are wired to the terminal strip on the integrated control 

in the furnace. Figure 15 (page 22) contains the proper 

connections for heating only (two-wire) and heating/

cooling  (four-wire)  applications.  Recommended 

minimum wire gauge for thermostat wiring is shown 

in Table 4 (page 22).

•  The  thermostat  should  be  mounted  about  5  feet 

above the floor on an inside wall. DO NOT install the 

thermostat  on  an  outside  wall  or  any  other  location 

where its operation may be adversely affected by radiant 

heat from fireplaces, sunlight, or lighting fixtures, and 

convective heat from warm air registers or electrical 

appliances.  Refer  to  the  thermostat  manufacturer’s 

instruction sheet for detailed mounting information.

Содержание CMF95 Series

Страница 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respec...

Страница 2: ...Base 13 MA 100 Universal Base Installation 14 Installing the Furnace on an MA 100 Base 15 Condensate Drainage 15 GAS SUPPLY PIPING 16 Leak Check 16 High Altitude Application 17 Converting to LP Propan...

Страница 3: ...ersonal injury or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code ANSI Z223 1 NFPA...

Страница 4: ...uses the appliance orequipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used andifapplicable aproduct approvedairintakemust be us...

Страница 5: ...tworkshouldbeappropriatelysizedtothecapacity of the furnace to ensure its proper airflow rating For installations above 2 000 ft the furnace should have a sea level input rating large enough that it w...

Страница 6: ...SSEMENT RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONED Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l emp...

Страница 7: ...t be known When estimating the length of vent runs consideration must be made to the effect of elbows and other fittings This is conveniently handled using the idea of equivalent length Thismeansthefi...

Страница 8: ...mination to windows and building air intakes Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes A vent terminal must be...

Страница 9: ...hown in Figure 4 The roof penetration mustbeproperlyflashedandwaterproofedwithaplumbing roof boot or equivalent flashing Vent and combustion air piping may be installed in an existing chimney which is...

Страница 10: ...I VentilAire IV Figure 5 VentilAire III IV Vent Freezing Protection CAUTION When the vent pipe is exposed to temperatures below freezing i e when it passes through unheated spaces chimneys etc the pip...

Страница 11: ...vent leakage It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant Requirements for sealing ducts vary from region to region Consult with local co...

Страница 12: ...CAUTION HAZARD OF ASPHYXIATION DO NOT COVER OR RESTRICT FLOOR RETURN AIR OPENING or equivalent For closet installation with less than 6 front clearance but not less than 1 a louvered door must be used...

Страница 13: ...fastenthefrontofthefurnace and the base to the floor with 8 x 1 2 sheet metal screws FURNACE INSTALLATION NOTE Sinceallinstallationsaredifferent thesequenceof these steps may differ from the actual in...

Страница 14: ...opening and center the top of the feeder duct in 14 1 8 x 14 1 8 floor opening 5 Using the feeder duct as a guide mark and cut a 12 x 12 opening in the supply duct Remove the base and transition feede...

Страница 15: ...will cause improper operation or damage to the furnace It is recommended that all drain lines on the outside of the residence be wrapped with an industry approved insulation or material allowed by loc...

Страница 16: ...l gas hookups are shown in Figure 12 Leak Check FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be pe...

Страница 17: ...nstallation may only be accomplished withfactorysuppliedorifices Donotattemptto drill out orifices in the field Improperly drilled orifices may cause fire explosion carbon monoxide poisoning personal...

Страница 18: ...ple Elevation 5 000 feet Type of Gas Natural Gas Local Heating Value of Gas 750 From Table 10 find 750 and follow down the column stop at the 5 000 feet row The heating value listed is LOW Table 12 wi...

Страница 19: ...ten until snug Make sure LP is visible after conversion Gas Pressure Verification Measuring the Supply Gas Pressure 1 Turn OFF the gas supply at the manual valve located on the outside of the unit 2 U...

Страница 20: ...are lit check all gas connections for leaks again with the soap and water solution Measuring the Manifold Pressure The manifold pressure must be measured by installing a pressure gauge Manometer Magn...

Страница 21: ...tothefurnace nameplate or Table 4 An electrical disconnect must be installed readily accessiblefromandlocatedwithinsightofthefurnace See Figure 18 page 29 or the wiring diagram label inside of the con...

Страница 22: ...otection2 045 45 000 18 115 60 1 127 103 11 0 14 20 13 1 21 7 072 72 000 18 115 60 1 127 103 10 4 14 20 12 4 20 4 NOTE Minimum wire gauge and maximum fuse circuit breaker amperage are based on MCA1 an...

Страница 23: ...e input rate in Btuh See example 6 The manifold pressure must be set to the appropriate valueforeachinstallationbyaqualifiedinstaller service agency or the gas supplier WARNING Do not attempt to drill...

Страница 24: ...nutes before taking any temperature readings The temperature rise is the difference between the supply and return air temperatures Verifying Burner Operation CAUTION The door over the burners may only...

Страница 25: ...alve and inducer remains energized The control goes to blower on delay 8 If flame is present the control energizes the blower on theselectedHEATspeed30secondsafterthegasvalve opened The gas valve and...

Страница 26: ...piping at the furnace 6 Remove the piping between the gas valve and the ground joint union If applicable 7 Remove the burner box door 6 screws 8 Remove 4 screws securing the manifold assembly to the b...

Страница 27: ...Fault Flash On Open Limit Switch Fault Flash Off Motor Fault On Off Diagnostic Description Yellow LED Low Flame Sensor Signal Continuous Flash Flame Present On Table 6 Control Board Fault Conditions...

Страница 28: ...8 1 3 8 1 5 8 24 3 16 4 3 4 2 7 8 1 3 4 1 3 4 16 1 2 13 5 8 3 1 2 X 1 1 2 Slots for Gas Pipe Condensate drains Typ FRONT VIEW LEFT SIDE TOP VIEW BOTTOM VIEW 3 3 4 Dia 2 Places 32 2 7 8 Dia Hole for Li...

Страница 29: ...SINGLE STAGE THERMOSTAT TO OUTDOOR UNIT FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM For 80 and 90 Single Stage Furnaces Refer to the Installation Instructions provided with the furnac...

Страница 30: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Страница 31: ...T BTU 45 000 72 000 0 to 1 999 FT 49 47 2 000 to 2 999 FT 50 48 3 000 to 3 999 FT 50 48 4 000 to 4 999 FT 51 48 5 000 to 5 999 FT 51 49 6 000 to 6 999 FT 51 49 7 000 to 7 999 FT 52 50 8 000 to 8 999 F...

Страница 32: ...ls All Clearances in this Figure apply on both walls G Clearance to inside corner All Clearances in this Figure apply on both walls All Clearances in this Figure apply on both walls H Clearance to eac...

Страница 33: ...ble Wall Normal Snow Level COMBUSTION AIR Seal Caulk Around Pipes at Building 90 Elbow 7 12 Min 90 Elbow 90 Elbow Support System on Vertical Rise FLUE PIPE COMBUSTION AIR See Table 2 for PVC Pipe Leng...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...efully before starting the installation Return these instructions to the customer s package for future reference PROPOSITION 65 WARNING This product contains chemicals known to the state of California...

Отзывы: