Instruction manual
OCM Pro CF
page 88
OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 9-33
Sensor type 1: air-ultrasonic
Sensor type 2:
Water-ultrasonic (Water-US internal)
Level measurement using a combi sensor type V1H or V2H. Level measurement
using water-ultrasound from bottom up.
This sensor type is for discharge detection in medium part filled areas.
The sensor must be installed exactly in the bottom centre observing a maximum
permissible deviation of ±2°.
Important Note
Never use a water-ultrasonic sensor if the sensor is installed out of the centre,
(e.g. sedimentation or risk of soiling)! This may result in echo loss and meas-
urement failure.
In this case use a different level sensor (ultrasound from top down or pressure
measurement cell).
Fig. 9-34
Sensor type 2: water-ultrasonic
Sensor type 3:
2-Wire probe EX
This selection is for level measurement by using external 2-wire Ex probes sup-
plied by OCM Pro CF such as a pressure probe type NivuBar Plus or a type
NivuCompact echo sounder. Can be combined with the flow velocity sensor.