Instruction manual
OCM Pro CF
®
OCM Pro CF - Rev. 09 as of 07.06.2016
page 119
Fig. 9-87
Enabling quick close function
Fig. 9-88
Quick close parameters
Q
max
and h
max
operate as OR parameters. Depending on application they have to
be set 10-50 % higher than the condition established when the system falls to
regulator mode during dry weather operation.
T
max
is the time the control unit requires to move from open position to the
standard position during control operation mode.
Automatic
flush function
This function allows to frequently flush the measurement section during dry
weather operation. In order to dam up the medium and to generate a flush
surge, set
Days
and
Time
of the control unit to be closed. The control unit will
open up again after the
Impounding Duration
(to be set) has expired and will
remain in open condition as long as the
Duration of Flush
has been set. This
sequence will be repeated subsequently.
The number of
flush events
can be set from 1 to 9.
Fig. 9-89
Enabling the flush function
Note
The flush function is not available during active control operation.