16
– English
5.2 - Standard Setup
The control unit contains one selector and 3 buttons: these behave differently depending on the status of the programming selector.
Functions with PROG selector (SPYBOX B/V1)
I
O
I
O
OPERATION DURING PROGRAMMING
Note: LEDs L1...L8 indicate the status of the active functions
ON
: function active
OFF
: function NOT active
FLASHING
: procedure under way (e.g. L1+L2 = device acquisition
under way)
I
O
I
O
NORMAL OPERATION
Note: the LEDs L1 ... L8 remain off
key
function
key
function
OPEN
shifts the programming point to the left
OPEN
commands and opening manoeuvre
STOP
- accesses the programming phase
- modifies the parameter
STOP
- stops the current manoeuvre
- with the motor stationary, it inverts the status of the
courtesy light (SPYLIGHT)
CLOSE
shifts the programming point to the right
CLOSE
commands a closing manoeuvre
CAUTION! - With the selector set to the left (in programming mode, therefore), no movement command can be imparted to the
motor. To move the motor, shift the selector back to the right (Normal Operation mode).
5.3 - Device Acquisition
After connecting the power supply, if you have not run the Quick Setup (section 5.1), it is necessary to carry out the acquisition of the devices
connected to the STOP input (indicated by the flashing of the LEDs L1 and L2).
If you use a category B resistive sensitive edge (according to EN13849-1, -2) to limit the impact force (according to CAT 2 and
Performance Level C), you must activate parameter L5 (level one programming) and then perform the device search procedure.
CAUTION! - During this procedure, the control unit switches the internal relays to run a few functional tests.
CAUTION! - The device acquisition phase must be performed even if there is no device connected.
01.
02.
03.
I
O
I
O
(OPEN + STOP) 3 s = L1 + L2
I
O
I
O
The acquisition memorises the sta-
tus of the ALT input
5.4 - Acquisition of Opening and Closing Positions
After acquiring the devices (section 6.2) it is necessary to enable the control unit to recognize the opening and closing positions of the garage
door.
In this phase, the length of the stroke of the garage door is measured, from the closing mechanical stop to the opening mechanical stop.
CAUTION! - If the first manoeuvre to be carried out is an Opening manoeuvre, interrupt the procedure and invert – on the control
unit – the electrical connections on the motor terminal. Repeat the procedure from point 1.
01.
02.
03.
I
O
I
O
(STOP + CLOSE) 3 s = L3 + L4
Start manoeuvres: close, open and close.
During this sequence the positions are memo-
rised
I
O
I
O
5.5 - Deletion of parameters memory
01.
02.
03.
04.
I
O
I
O
(OPEN + CLOSE) 3 s
L1
=
(OPEN + CLOSE)
Start deleting all
memory except radio
codes (section 6.5)
I
O
I
O
5.6 - Parameter programming (ON-OFF)
IMPORTANT!
- The parameter modification procedures must be completed within maximum 10 seconds from the start of the execution: you
must therefore first read the legend contained in the following paragraphs and then proceed.
During normal operation, in other words when the control unit
is not in ‘parameter programming’
mode, LEDs ‘L1 ... L8’ are always switched
off. When the user enters the programming mode, LEDs ‘L1 ... L8’ indicate
the status of the respective function; for example, ‘L1’ is lit
when the ‘Automatic Closing’ function is enabled.