SLIDESMART CNX 15 BASIC MANUAL
www.hysecurity.com
15
Figure 6. Conduits and Earth Ground
Figure 7.
Preferred Control Wire Routing to SmartCNX Controller
PREPARE AN INSTALLATION SITE
CONDUITS STUBBED
MIN. 2” ABOVE PAD
GROUND LEVEL
INCOMING
HIGH VOLTAGE
VEHICLE
LOOP
CONTROL
WIRES
LOW VOLTAGE/
COMMUNICATION
WIRES
PRIMARY/SECONDARY
WIRES - OPTIONAL
EARTH
GROUND
CONDUIT
3 FOOT
(91cm)
MAXIMUM
Earth
Ground
rod & wire
Consult local
codes for
proper depth
The potential for
lightning discharge
exists with all gates, fences, and
gate operators. National Electric
Code (NEC) requires a separate
earth ground in addition to the
required equipment ground. A local
earth ground also serves to protect
the electronic controls.
DANGER
NOTE:
To reduce electrical
interference, keep as much distance
as possible between the high voltage
and low voltage conduits.
ROUTE 6 AWG
EARTH GROUND
WIRE THROUGH
CONDUIT AND
ATTACH TO
PROVIDED
GROUND LUG
HySecurity requires a concrete pad
with a minimum 2 inch extension above
ground and a pad depth of 16 inch or
at least to the frost line, whichever is
deeper. Follow local building codes to
identify the frost line.