35
Example 3:
Setpoint 1 = 300,
Setpoint 2 = 200
Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” =
Red
Display Colors change sequences:
AMBER
|
AMBER
|
AMBER
|
GREEN
|
AMBER
•
u
--------------• ------• ------• --------------------------------• -------• -------• -------------------
u
0 190 200 210 290 300 310
Alarm 1 is designed to monitor the Process Value around the
Setpoint 1. Alarm 2 is designed to monitor the Process Value around
the Setpoint 2.
Example 4:
Setpoint 1 = 200
Setpoint 2 = 200
Alarm 1 Setup: Deviation, Band, “ALR.H” = 20
Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” =
Red
Display colors change sequences:
AMBER
|
RED
|
GREEN
|
GREEN
|
RED
|
AMBER
•
u
------------------• ---------------• --------------• -------------• -------------• -------------------
u
0 180 195 200 210 220
Reset:
The instrument automatically resets after the last menu of the
Configuration Mode has been entered. After the instrument resets, it
advances to the Run Mode.